ENGLISH

EN

 

-

Choose between the options suggested and confirm your choice.

ANTI-CYCLE FUNCTION

RESET CH TIMERS

DHW THERMOSTAT

PARAMETERS

INSTALLER

PRE-HEATING

 

-

ANTI-CYCLE FUNCTION: 

this parameter allows you to change the ANTI-CYCLE 

FUNCTION, regarding the delay time introduced for re-igniting the burner in the face of 

an off due to the heating temperature being reached. The factory setting is 3 minutes and  

can be set and confirmed to a value between 0 min and 20 min.

3

MIN

ANTI-CYCLE FUNCTION

 

-

RESET CH TIMERS:

  this parameter allows you to reset the REDUCED HEATING 

MAXIMUM OUTPUT TIMING, during which the speed of the fan is limited to 75% of the 

maximum heating output that has been set, and the FORCED HEATING TIMING OFF. 

The factory setting is

 FUNCTION NOT ACTIVE, select FUNCTION ACTIVE and confirm the 

choice for resetting the timings.

FUNCTION ACTIVE

INSTALLER

FUNCTION NOT ACTIVE

RESET CH TIMERS

 

-

DOMESTIC HOT WATER THERMOSTATS:

 this parameter allows you to set the type 

of DOMESTIC HOT WATER THERMOSTATS. The factory setting is RELATED, i.e. for 

domestic hot water the boiler switches off at se5°C and restarts at se4°C. 

Selecting ABSOLUTE value, the boiler for  domestic hot water will still switch off at 65°C 

and restart at 63°C. 

RELATED

ABSOLUTE

INSTALLER

DHW THERMOSTAT

 

-

PREHEATING:

 parameter PREHEATING = 1 (function active, P symbol on steady). 

This function keeps the water in the domestic hot water exchanger hot, to reduce 

standby times when a request is made. During a pre-heating request, the P symbol 

starts flashing. With PREHEATING = 0, the symbol P switches off aand the function is 

deactivate. The function is not active when the boiler is OFF.

0

PREHEATING

 

-

TOUCH & GO:

 

if you do not want PREHEATING to be always active and you want 

hot water immediately ready, it is possible to preheat the domestic hot water just a 

few moments before taking it. Set the parameter to PREHEATING = 2, to activate the 

TOUCH&GO function. This function allows you, by opening and closing the tap, to start 

the instantaneous pre-heating that prepare the hot water only for that water take.

 

-

DHW DELAY:

  this parameter allows you to set the delayed starting of the boiler 

in domestic hot water mode. The factory setting of this parameter is 0 and can be 

programmed within the range 0 - 60 sec.

 

-

DO_AUX1:

 through this value it is possible to configure the functions associated with the 

digital output used to manage the additional pump and the zone valve. The factory setting 

for this parameter is 0 and can be set within the 0 - 2 range with the following meaning:

Pin 1 and 2 of X21 Jumper not present

Jumpered

DO_AUX1 = 0

additional pump management

zone valve management

DO_AUX1 = 1

zone valve management

zone valve management

DO_AUX1 = 2

additional pump management

additional pump management

 

-

CONGIF OTBUS

this parameter is used to enable the remote control of the boiler via 

an OpenTherm device:

  1 = FACTORY VALUE. OTBus function enabled. The message “OPEN THERM 

CONNECTED” will appear on the display, when an OTBus device connected.

 

b

The OpenTherm connection is not enabled in the presence of a heat pump.

  0 = OTBus function disabled. If this parameter is set at 0, any possible OTBus 

connection is instantaneously interrupted.

4.2.2 

Configuration

 of the zone

It is possible to customise the management of the heating zone by accessing the ZONES 

MANAGER menu.

 

-

Access to menu TECHNICAL 

 INSTALLATION 

 ZONES MANAGER 

 

MODIFY ZONE.

PARAMETERS

WEATHER COMPENSATION

INSTALLATION

RANGE RATED

CALIBRATION

INSTALLER

TECHNICAL

SENSOR CALIBRATION

ZONES MANAGER

SYSTEM RESET

INSTALLER

INSTALLATION

ADD ZONE

MODIFY ZONE

DELETE ZONE

INSTALLATION

INSTALLER

 

-

Select the desired heating zone and then choose from the following options:

MAIN

INSTALLER

INSTALLATION

 

-

TYPE OF ACTUATION:

 set the parameter in question to ITRF05/AKM (default value)

 

-

TYPE OF HEAT REQUEST: 

this parameter allows you to specify the type of heat 

request, it is possible to choose from among the following options:

 THERMOSTAT

 (factory setting): the heat request is generated with an ON/OFF 

thermostat

  REC10CH MASTER

: the heat request to the boiler is generated by the REC10CH 

MASTER that assumes the function of MACHINE INTERFACE

 

-

TYPE OF ZONE:

 this parameter allows you to specify the type of zone to be heated, it 

is possible to choose from among the following options:

  HIGH TEMPERATURE (factory setting) 

  LOW TEMPERATURE

 

-

MIN SET HEAT;

 

this parameter allows you to specify the minimum heating setpoint that 

is possible (range 20°C - 80.5°C, default 20°C for high temperature systems - range 

20°C - 45°C, default 20°C for low temperature systems)

 

-

MAX SET HEAT:

 

this parameter allows you to specify the maximum heating setpoint that 

is possible (range 20°C - 80.5°C, default 80.5°C for high temperature systems - range 

20°C - 45°C, default 45°C for low temperature systems)

 

-

CHANGING NAME:

 

this parameter allows you to attribute a specific name to the heating zone

 

-

POR: 

this parameter allows you to enable the central heating programming timing for the 

zone concerned if the heat request is carried out using a room thermostat.

 

Programming timing not enabled = 0

  When the room thermostat contact closes the heat request is always met without any 

time band limitation.

 

Programming timing enabled = 1

  When the room thermostat contact closes the heat request is enabled according to the 

programming timing.

 

Note

: In this case make sure that the operating mode of the zone is set to AUTO in the 

STATE menu.

4.2.3 

Time band scheduling function

Set up the REC10CH for the time schedule, setting the parameter POR = 1 (see “4.2.2 

Configuration of the zone”). Set the time slots by selecting from the main screen MENU 

 

TIME SCHEDULE

TIME SCHEDULE

SETTINGS

SELECT OPTION

MENU

MAIN

MON

12/04/2021

12:17

SCHEDULE

START

END

THURSDAY

ZONE SCHEDULE

SELECT A DAY

07:30

08:30

11:30

13:30

18:30

22:30

MAIN

Programming: for each day of the week it is possible to set up to 4 bands, characterized by a 

start time and an end time. 

Note

: For more details on the use of the programming timing see 

the USER MANUAL of the REC10CH.

4.2.4 

Setting the thermoregulation

Thermoregulation only works with the outdoor temperature sensor installed/connected  and 

active only for the HEATING function. The temperature measured by the outdoor temperature 

sensor is displayed on the initial page in the top right, alternating with the display of the time. 

When thermoregulation is enabled (outdoor temperature sensor present), the algorithm for 

automatically calculating the outlet setpoint depends on the type of heat request

In any case, the 

thermoregulation algorithm will not directly use the outdoor temperature, but rather a calculated 

outdoor temperature that takes into account the building’s insulation: in buildings that are well 

insulated, the outdoor temperature variations will have less impact than those that are poorly 

insulated by comparison. 

Enabling THERMOREGULATION occurs in the following way:

 

-

select TECHNICAL 

 WEATHER COMPENSATION.

RANGE RATED

WEATHER COMPENSATION

PARAMETERS

INSTALLATION

CALIBRATION

INSTALLER

TECHNICAL

Содержание 20187642

Страница 1: ...Family KIS EN INSTALLER AND USER MANUAL...

Страница 2: ...ser also Warning This instructions manual contains data and information for both the user and the installer Specifically note that the user for the use of the appliance must refer to chapters Warnings...

Страница 3: ...this case ventilate the room by opening the doors and windows close the fuel shut off device ask the Technical Assistance Service or professionally qualified personnel to intervene promptly a It is f...

Страница 4: ...pe and consider any increase in the diameter of the pipe itself The condensation exhaust pipe must always have an adequate slope level to prevent the condensation from stagnating and its proper draina...

Страница 5: ...and immediately before and after each change of direction curve b The boiler is supplied without the flue gas exhaust air suction kit since it is possible to use the accessories for condensing applia...

Страница 6: ...e can exceed the static pressure of the collective air duct of 25 Pa in the condition in which n 1 boilers work at maximum rated heat input and 1 boiler at the minimum rated heat input allowed by the...

Страница 7: ...e vent cycle Remove any air in the domestic system radiators zone manifolds etc using the bleed valves Once again check that the system pressure is correct ideally 1 1 5 bar and restore the levels if...

Страница 8: ...is in progress number 1 is flashing This icon indicates that the circuit for domestic hot water production is enabled When a domestic hot water request is in progress the icon flashes The P at the to...

Страница 9: ...LER CHANGE NAME INSTALLER PI PROPORTIONAL 5 0 99 SERVICE only mixing zones with ACTUATION BE16 PI INTEGRAL 10 0 99 SERVICE only mixing zones with ACTUATION BE16 VALVE RUN 120 sec 0 sec 120 sec SERVICE...

Страница 10: ...request type TA and zone type HT 0 4 0 2 0 8 INSTALLER if EXTERNAL PROBE request type TA and zone type LT 2 0 1 0 5 0 INSTALLER if request type AMBIENT PROBE or REC10CH AMBIENT INFLUENCE 10 0 20 INSTA...

Страница 11: ...DISABLE COOLING FUNCTION NOT ACTIVE FUNCTION ACTIVE FUNCTION NOT ACTIVE INSTALLER USE FOR DHW DON TUSE FOR DHW DHW FUNCTION NOT ACTIVE DHW FUNCTION ACTIVE DHW FUNCTION NOT ACTIVE INSTALLER if BE17 pre...

Страница 12: ...t it has all the safety and control devices required by current regulations that the circulator rotates freely because especially after long periods of inactivity deposits and or debris can prevent fr...

Страница 13: ...ZONE PARAMETERS WEATHER COMPENSATION INSTALLATION RANGE RATED CALIBRATION INSTALLER TECHNICAL SENSOR CALIBRATION ZONES MANAGER SYSTEM RESET INSTALLER INSTALLATION ADD ZONE MODIFY ZONE DELETE ZONE INS...

Страница 14: ...URE C EXTERNAL TEMPERATURE C NIGHT COMPENSATION If a timer is connected to the ROOM THERMOSTAT input the NIGHT COMP function can be enabled as follows menu TECHNICAL WEATHER COMPENSATION CLIMATIC CURV...

Страница 15: ...in standby again keeping the outlet temperature displayed If faults arise in ignition or operations the boiler performs a SAFETY STOP the triangle signalling faults will flash on the REC10CH To identi...

Страница 16: ...Technical Assistance Centre 4 13 Gas conversion Conversion from a family gas to other family gas can be performed easily also when the boiler is installed This operation must be carried out by profes...

Страница 17: ...l E042 water pressure transducer fault definitive E060 domestic hot water probe fault transitional E070 flow sensor faulty flow sensor overtemperature flow return sensor differential alarm transitiona...

Страница 18: ...TECHNICAL Note After a reset it is necessary to carry out a new configuration of the system for details about this procedure see the following section 4 19 System configuration b This operation must b...

Страница 19: ...in intact and to comply with prescriptions of current regulations it is necessary to render the appliance to systematic checks at regular intervals When carrying out maintenance work observe the instr...

Страница 20: ...nnect the tubes A and B remove the clip C and remove the siphon Unscrew the bottom and top caps then remove the float Clean the parts of the siphon from any solid residues b Do not remove the safety s...

Страница 21: ...EFAULT VALUE FACTORY SET MINIMUM VALUE MAXIMUM VALUE ACCESS LEVEL NOTES MENU SETTINGS USER TIME DATE USER DAYLIGHT SAVINGS TIME FUNCTION ACTIVE FUNCTION NOT ACTIVE FUNCTION ACTIVE USER LANGUAGE ITALIA...

Страница 22: ...ed programme 8 2 3 MANUAL If MANUAL is selected the zone requests will be managed based on the setpoint set by the user 8 2 4 HEAT OFF If HEAT OFF is selected the zone requests will not be fulfilled N...

Страница 23: ...0 INFO The INFO function can be used to display a series of data regarding the system ATTENTION The displayed data cannot be modified SCREED HEATER OPERATING HOURS DELIVERY PROBE RETURN PROBE DOMESTIC...

Страница 24: ...TART THURSDAY USE THE ARROWS TO MODIFY ENTER START TIME ADD PERIOD END MAIN Once the operation completed the display will show 07 30 08 30 11 30 14 00 13 30 15 00 18 00 22 30 START THURSDAY ADD MODIFY...

Страница 25: ...TURE WILL BE ADJUSTED WITH NEW TARGET SET POINT UNTIL 09 04 2021 ON 13 15 1 ZONE1 CONFIRM CANCEL 00 30 YOU ARE ACTIVATING COMFORT MODE ENTER TIME DURATION IN HOURS USE THE ARROWS TO MODIFY 1 ZONE1 26...

Страница 26: ...Maximum pressure bar 8 8 8 Minimum pressure bar 0 15 0 15 0 15 Quantity of hot water with t 25 C 30 C 35 C l min 15 1 12 5 10 8 18 1 15 1 12 9 20 8 17 4 14 9 DHW minimum capacity l min 2 2 2 Selectio...

Страница 27: ...ith reference to Delegated Regulation EU No 811 2013 the data in the table can be used for completing the product card and the labelling for ambient heating appliances for mixed heating appliances for...

Страница 28: ...ivery 34 Hot water 35 Gas 36 Heating return 37 Cold water 2 21 AF AC M R 20 19 1 6 6 8 9 5 4 6 7 3 2 18 15 14 13 12 11 10 16 17 15 3 Residual head of circulator Fig 3 A B C Residual head mbar Flow rat...

Страница 29: ...entering a value 10 the circulator speed will change to achieve a system flow rate with the aim of maintain ing the T of 10 C upstream and down stream of the exchanger 3 CIRCULATOR IN MAXIMUM FIXED S...

Страница 30: ...Wiring diagram Blu Blue Marrone Brown Nero Black Rosso Red Bianco White Viola Violet Rosa Pink Arancione Orange Grigio Grey Giallo Yellow Verde Green A Gas valve B 230V auxiliary C Voltage free contac...

Страница 31: ...from 60 100 to 80 80 110 65 65 1 1 5 90 bend 60 100 60 100 horizontal 10 horizontal 6 horizontal 6 1 3 1 6 105 vertical 11 vertical 7 vertical 7 90 bend 80 125 80 125 25 15 15 1 1 5 130 adaptor from 6...

Страница 32: ...T OPTION 4 and SYSTEM INFO INSTALLATION WEATHER COMPENSATION RANGE RATED TECHNICAL INSTALLER 5 PARAMETERS CALIBRATION and ANTI CYCLE FUNCTION RESET CH TIMERS DHW THERMOSTAT PARAMETERS INSTALLER 6 PUMP...

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ...Cod 20187595 09 21 Ed 3...

Отзывы: