Riello 20187642 Скачать руководство пользователя страница 5

5

ENGLISH

EN

 

b

The earth conductor must be a couple of cm longer than the others.

 

b

To create the seal of the boiler use a clamp and tighten it on the cable grommet used.

The boiler can operate with a phase-neutral or phase-phase power supply. 

It is forbidden to use gas and/or water pipes to earth electrical appliances.

Use the power cable supplied to connect the boiler to the mains power supply. If the power 

cable has to be replaced, use a HAR H05V2V2-F, 3 x 0.75mm² cable, Ø max external 7 mm.

2.5 

Gas connection

The connection of the gas supply must be carried out in compliance with current installation 

standards. Before carrying out the connection, check that the type of gas is that for which 

the appliance is set up.

2.6 

Removing the casing

To access the components inside, remove the casing as shown in the figure.

 

b

If removing the side panels, put them back in their initial position, referring to the 

adhesive label on its wall.

 

b

If the front panel is damaged it must be replaced.

 

b

The noise absorbing panels inside the front and side walls ensure the airtight seal for the 

air supply duct in the installation environment.

 

b

It is therefore CRUCIAL after the dismantling operations to correctly reposition the 

components to ensure the boiler's seal is effective.

B

B

C

C

A

2.7 

Flue gas exhaust and combustion air suction

To evacuate the combustion products, refer to UNI 7129-7131. Always comply with 

local standards of the Fire Department, the Gas Company and with possible municipal 

dispositions. It is essential for the evacuation of the flue gases and the adduction of the 

boiler's combustion air that only original pipes be used (except C6) and that the connection 

is made correctly as shown in the instructions provided with the flue gases accessories. 

A single flue can be connected to several appliances provided that every appliance is the 

condensing type.

 

b

 

b

The straight length includes the first bend (connection into the boiler), terminals 

and joints. An exception is made for the vertical Ø 60-100 mm coaxial pipe, whose 

straight length excludes bends.

 

b

To ensure greater installation safety, fix the ducts to the wall (wall or ceiling) using 

special fixing brackets to be positioned at each joint, at a distance such as not to 

exceed the length of each individual extension and immediately before and after 

each change of direction (curve).

 

b

The boiler is supplied without the flue gas exhaust/air suction kit, since it is possible 

to  use  the  accessories  for  condensing  appliances  that  best  fit  the  installation 

characteristics (see RIELLO catalogue).

 

b

The maximum lengths of the pipes refer to the flue accessories available in the 

RIELLO catalogue.

 

b

It is compulsory to use specific pipes.

 

b

The non insulated flue gas outlet pipes are potential sources of danger.

 

b

The use of a longer pipe causes a loss of output of the boiler.

 

b

The exhaust pipes can face in the direction most suited to the installation 

requirements.

 

b

As envisaged by current legislation, the boiler is designed to take in and dispose of 

flue gas condensate and/or meteoric water condensate deriving from the flue gas 

discharge system using its own siphon.

 

b

If a condensate relaunch pump is installed, check the technical data (provided by the 

manufacturer) regarding output, to ensure it operates correctly.

 

-

Position the discharge pipe so that the connection sits fully up against the flugases turret 

of the boiler.

 

-

After positioning it, make sure the 4 notches (

A

) slip into the groove (

B

).

 

-

Fully tighten the screws (

C

) that hold the two flange locking terminals, so thbend itself is 

restrained held in place.

B

B

B

B23P-B53P

Ø60-100

Ø80-80

A

A

C

C

B

B

Ø80-125

 

b

If the Ø 60-100 to Ø 80-80 splitter kit is used instead of the twin pipe system, there 

is a loss in the maximum lengths as shown in the table.

Ø50

Ø

60

Ø80

Loss of length (m)

0.5

1.2

5.5 for flue gases pipe

7.5 for air pipe

Twin pipes with Ø 80 pipework Ø50 - Ø60 - Ø80)

Thanks to the boiler characteristics, a Ø80 flue gas exhaust pipe can be connected to 

the Ø50 - Ø60 - Ø80 piping ranges.

 

b

For the pipe, you are advised to make a project calculation in order to respect the 

relevant regulations in force.

The table shows the standard configurations allowed.

Air suction

1 Bend 90° Ø 80

4.5m pipe Ø80

Flue gas discharge

1 Bend 90° Ø 80

4.5m pipe Ø80

Reduction from Ø80 to Ø50 from Ø80 to Ø60

Flue base bend 90°, Ø50 or Ø60 or Ø80

For ducting pipe lengths see table

The boilers are factory set to:

CH rpm

DHW rpm

Max length pipes (m)

Ø50

Ø60

Ø80

25 KIS

6.200

7.600

5

18

98

30 KIS

5.800

6.900

2

11

53

35 KIS

7.300

7.800

2

11

57

Should greater lengths be required, compensate the pressure drop with an increase in the 

r.p.m.of the fan, as shown in the adjustments table, to provide the rated heat input, referring 

to paragraph “3.9 Adjustments”.

 

b

The minimum calibration should not be modified.

Содержание 20187642

Страница 1: ...Family KIS EN INSTALLER AND USER MANUAL...

Страница 2: ...ser also Warning This instructions manual contains data and information for both the user and the installer Specifically note that the user for the use of the appliance must refer to chapters Warnings...

Страница 3: ...this case ventilate the room by opening the doors and windows close the fuel shut off device ask the Technical Assistance Service or professionally qualified personnel to intervene promptly a It is f...

Страница 4: ...pe and consider any increase in the diameter of the pipe itself The condensation exhaust pipe must always have an adequate slope level to prevent the condensation from stagnating and its proper draina...

Страница 5: ...and immediately before and after each change of direction curve b The boiler is supplied without the flue gas exhaust air suction kit since it is possible to use the accessories for condensing applia...

Страница 6: ...e can exceed the static pressure of the collective air duct of 25 Pa in the condition in which n 1 boilers work at maximum rated heat input and 1 boiler at the minimum rated heat input allowed by the...

Страница 7: ...e vent cycle Remove any air in the domestic system radiators zone manifolds etc using the bleed valves Once again check that the system pressure is correct ideally 1 1 5 bar and restore the levels if...

Страница 8: ...is in progress number 1 is flashing This icon indicates that the circuit for domestic hot water production is enabled When a domestic hot water request is in progress the icon flashes The P at the to...

Страница 9: ...LER CHANGE NAME INSTALLER PI PROPORTIONAL 5 0 99 SERVICE only mixing zones with ACTUATION BE16 PI INTEGRAL 10 0 99 SERVICE only mixing zones with ACTUATION BE16 VALVE RUN 120 sec 0 sec 120 sec SERVICE...

Страница 10: ...request type TA and zone type HT 0 4 0 2 0 8 INSTALLER if EXTERNAL PROBE request type TA and zone type LT 2 0 1 0 5 0 INSTALLER if request type AMBIENT PROBE or REC10CH AMBIENT INFLUENCE 10 0 20 INSTA...

Страница 11: ...DISABLE COOLING FUNCTION NOT ACTIVE FUNCTION ACTIVE FUNCTION NOT ACTIVE INSTALLER USE FOR DHW DON TUSE FOR DHW DHW FUNCTION NOT ACTIVE DHW FUNCTION ACTIVE DHW FUNCTION NOT ACTIVE INSTALLER if BE17 pre...

Страница 12: ...t it has all the safety and control devices required by current regulations that the circulator rotates freely because especially after long periods of inactivity deposits and or debris can prevent fr...

Страница 13: ...ZONE PARAMETERS WEATHER COMPENSATION INSTALLATION RANGE RATED CALIBRATION INSTALLER TECHNICAL SENSOR CALIBRATION ZONES MANAGER SYSTEM RESET INSTALLER INSTALLATION ADD ZONE MODIFY ZONE DELETE ZONE INS...

Страница 14: ...URE C EXTERNAL TEMPERATURE C NIGHT COMPENSATION If a timer is connected to the ROOM THERMOSTAT input the NIGHT COMP function can be enabled as follows menu TECHNICAL WEATHER COMPENSATION CLIMATIC CURV...

Страница 15: ...in standby again keeping the outlet temperature displayed If faults arise in ignition or operations the boiler performs a SAFETY STOP the triangle signalling faults will flash on the REC10CH To identi...

Страница 16: ...Technical Assistance Centre 4 13 Gas conversion Conversion from a family gas to other family gas can be performed easily also when the boiler is installed This operation must be carried out by profes...

Страница 17: ...l E042 water pressure transducer fault definitive E060 domestic hot water probe fault transitional E070 flow sensor faulty flow sensor overtemperature flow return sensor differential alarm transitiona...

Страница 18: ...TECHNICAL Note After a reset it is necessary to carry out a new configuration of the system for details about this procedure see the following section 4 19 System configuration b This operation must b...

Страница 19: ...in intact and to comply with prescriptions of current regulations it is necessary to render the appliance to systematic checks at regular intervals When carrying out maintenance work observe the instr...

Страница 20: ...nnect the tubes A and B remove the clip C and remove the siphon Unscrew the bottom and top caps then remove the float Clean the parts of the siphon from any solid residues b Do not remove the safety s...

Страница 21: ...EFAULT VALUE FACTORY SET MINIMUM VALUE MAXIMUM VALUE ACCESS LEVEL NOTES MENU SETTINGS USER TIME DATE USER DAYLIGHT SAVINGS TIME FUNCTION ACTIVE FUNCTION NOT ACTIVE FUNCTION ACTIVE USER LANGUAGE ITALIA...

Страница 22: ...ed programme 8 2 3 MANUAL If MANUAL is selected the zone requests will be managed based on the setpoint set by the user 8 2 4 HEAT OFF If HEAT OFF is selected the zone requests will not be fulfilled N...

Страница 23: ...0 INFO The INFO function can be used to display a series of data regarding the system ATTENTION The displayed data cannot be modified SCREED HEATER OPERATING HOURS DELIVERY PROBE RETURN PROBE DOMESTIC...

Страница 24: ...TART THURSDAY USE THE ARROWS TO MODIFY ENTER START TIME ADD PERIOD END MAIN Once the operation completed the display will show 07 30 08 30 11 30 14 00 13 30 15 00 18 00 22 30 START THURSDAY ADD MODIFY...

Страница 25: ...TURE WILL BE ADJUSTED WITH NEW TARGET SET POINT UNTIL 09 04 2021 ON 13 15 1 ZONE1 CONFIRM CANCEL 00 30 YOU ARE ACTIVATING COMFORT MODE ENTER TIME DURATION IN HOURS USE THE ARROWS TO MODIFY 1 ZONE1 26...

Страница 26: ...Maximum pressure bar 8 8 8 Minimum pressure bar 0 15 0 15 0 15 Quantity of hot water with t 25 C 30 C 35 C l min 15 1 12 5 10 8 18 1 15 1 12 9 20 8 17 4 14 9 DHW minimum capacity l min 2 2 2 Selectio...

Страница 27: ...ith reference to Delegated Regulation EU No 811 2013 the data in the table can be used for completing the product card and the labelling for ambient heating appliances for mixed heating appliances for...

Страница 28: ...ivery 34 Hot water 35 Gas 36 Heating return 37 Cold water 2 21 AF AC M R 20 19 1 6 6 8 9 5 4 6 7 3 2 18 15 14 13 12 11 10 16 17 15 3 Residual head of circulator Fig 3 A B C Residual head mbar Flow rat...

Страница 29: ...entering a value 10 the circulator speed will change to achieve a system flow rate with the aim of maintain ing the T of 10 C upstream and down stream of the exchanger 3 CIRCULATOR IN MAXIMUM FIXED S...

Страница 30: ...Wiring diagram Blu Blue Marrone Brown Nero Black Rosso Red Bianco White Viola Violet Rosa Pink Arancione Orange Grigio Grey Giallo Yellow Verde Green A Gas valve B 230V auxiliary C Voltage free contac...

Страница 31: ...from 60 100 to 80 80 110 65 65 1 1 5 90 bend 60 100 60 100 horizontal 10 horizontal 6 horizontal 6 1 3 1 6 105 vertical 11 vertical 7 vertical 7 90 bend 80 125 80 125 25 15 15 1 1 5 130 adaptor from 6...

Страница 32: ...T OPTION 4 and SYSTEM INFO INSTALLATION WEATHER COMPENSATION RANGE RATED TECHNICAL INSTALLER 5 PARAMETERS CALIBRATION and ANTI CYCLE FUNCTION RESET CH TIMERS DHW THERMOSTAT PARAMETERS INSTALLER 6 PUMP...

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ...Cod 20187595 09 21 Ed 3...

Отзывы: