87
PRO-
EN
RESETCFG menu
Name
Format
Default
Units
Description
COOLING RESET
oatcr_no
-10 to 51.7
-10
°C
Outdoor air temperature for no compensation.
oatcr_fu
-10 to 51.7
-10
°C
Outdoor air temperature for full compensation.
dt_cr_no
0 to 13.9
0
^C
Temperature difference for no compensation
dt_cr_fu 0
0 to 13.9
0
^C
Temperature difference for full compensation
cr_deg
-16.7 to 16.7
0
^C
Compensation value in cooling mode.
HEATING RESET
oathr_no
-10 to 51.7
-10
°C
Outdoor air temperature for no compensation.
oathr_fu
-10 to 51.7
-10
°C
Outdoor air temperature for full compensation.
dt_hr_no
0 to 13.9
0
^C
Temperature difference for no compensation
dt_hr_fu
0 to 13.9
0
^C
Temperature difference for full compensation
hr_deg
-16.7 to 16.7
0
^C
Compensation value in heating mode.
USERCONF menu
Name
Format
Default
Units
Description
language
0 to 4
0
-
Language selection
English = 0
Spanish = 1
French = 2
Portuguese = 3
Italian =4
For translation = 5.
use_pass
1 to 9999
113
-
User password.
DATETIME menu
Name
Format
Default
Units
Description
hour
0 to 24
hours
Hours.
minutes
0 to 59
minutes
Minutes.
dow
1 to 7
Day of the week.
tom_hol
No/Yes
No
-
Is it holiday tomorrow?
tod_hol
No/Yes
No
-
Is it holiday today?
dlig_off
No/Yes
-
Is winter time change setting active?
dlig_on
No/Yes
-
Is summer time change setting active?
d_of_m
1 to 31
Day of the month.
month
1 to 12
Month.
year
0 to 99
Year.
CTRL_ID menu
Name
Format
Default
Units
Description
elemt_nb 1 -
1 to 239
1
-
Element number.
bus_nb
0 to 239
0
-
Bus number.
baudrate -
9600 to 38400
9600
Transmission speed.
PRO-
NXC / NXH
Description.
CSA-SR-20H430NN
-
Software version.
Serial number.