89
PRO-
EN
HOLIDAY menu
Use this function to set up to 16 holiday periods. Each period
is defined by the three parameters below:
• month.
• period starting day.
• period length.
Name
Format
Default
Units
Description
HOL_MON
0-12
0
-
Monthly holiday
HOL_DAY
0-31
0
-
Daily holiday
HOL_LEN
0-99
0
-
Holiday length
3.5 CHECK OPERATIONS
3.5.1 Start and stop controls
The table below compares the status of a series of
parameters according to the type of control present on the
unit, the operation mode selected and whether the unit is
in start or stop.
PARAMETER STATUS
TYPE OF
CONTROL
STATUS
UNIT
LOFF
L-ON
L-SC
rEM
CCN
MASt
CHIL_S_S
Remote
START/STOP
CONTACT
MASTER
CONTROL
TYPE
START/STOP
SCHEDULE
MODE
CCN
EMERGENCY
SHUTDOWN
GENERAL
ALARM
-
-
-
-
-
-
-
-
-
-
Enabled
-
-
Off
-
-
-
-
-
-
-
-
-
-
-
Yes
-
Off
Active
-
-
-
-
-
-
-
-
-
-
-
Local
Off
-
-
Active
-
-
-
-
-
-
Free
-
-
Local
Off
-
-
-
Active
-
-
-
Off
-
-
-
-
Remote
Off
-
-
-
Active
-
-
-
-
-
Free
-
-
Remote
Off
-
-
-
-
Active
-
Disabled
-
-
-
-
-
CNN
Off
-
-
-
-
Active
-
-
-
-
Free
-
-
CNN
Off
-
-
-
-
-
Active
-
-
Local
Free
-
-
Local
Off
-
-
-
-
-
Active
-
Off
Remote
-
-
-
Remote
Off
-
-
-
-
-
Active
-
-
Remote
Free
-
-
Remote
Off
-
-
-
-
-
Active
Disabled
-
RCN
-
-
-
CNN
Off
-
-
-
-
-
Active
-
-
RCN
Free
-
-
CNN
Off
-
Active
-
-
-
-
-
-
-
-
Disabled
No
Local
On
-
-
Active
-
-
-
-
-
-
Occupied
Disabled
No
Local
On
-
-
-
Active
-
-
-
Cooling
-
Occupied
Disabled
No
Remote
On
-
-
-
Active
-
-
-
Heating
-
Occupied
Disabled
No
Remote
On
-
-
-
Active
-
-
-
On auto
-
Occupied
Disabled
No
Remote
On
-
-
-
-
Active
-
Enabled
-
-
Occupied
Disabled
No
CNN
On
-
-
-
-
-
Active
-
-
Local
Occupied
Disabled
No
Local
On
-
-
-
-
-
Active
-
Cooling
Remote
Occupied
Disabled
No
Remote
On
-
-
-
-
-
Active
-
Heating
Remote
Occupied
Disabled
No
Remote
On
-
-
-
-
-
Active
-
On auto
Remote
Occupied
Disabled
No
Remote
On
-
-
-
-
-
Active
Enabled
-
RCN
Occupied
Disabled
No
CNN
On
3.5.2 Operating mode and parameters
Use the ON/OFF button to select the following
types:
• LOFF: Local off
• L-ON: Local on
• L-SC: local schedule
• rEM: remote
• CCN: network
• MASt: Master
• CHIL_S_S: operation mode active if the machine is in CCN
mode.
Parameters
• REMOTE START/STOP CONTACT: this parameter operates in
combination with contacts when the unit operates in re-
mote mode.
• MASTER CONTROL TYPE: This parameter is used when the unit is
a Master unit and determines its control type.
• START/STOP SCHEDULE: Parameter that establishes whether
the machine is busy or not, depending on if it is in start or
stop.
• CCN EMERGENCY SHUTDOWN: If the unit operation mode is of the
CCN type, this parameter turns unit off when it is in
shutdown phase.
• GENERAL ALARM: This parameter makes the unit completely
stop in case of a malfunction.