SETPOINT menu
Name
Format
Value
Units
Description
csp1
- 29.7 to 20
12.0
°C
Cooling setpoint 1.
csp2
- 29.7 to 20
12.0
°C
Cooling setpoint 2.
hsp1
20 to 55
40.0
°C
Heating setpoint 1.
hsp2
20 to 55
40.0
°C
Heating setpoint 2.
hramp_sp
0.1 to 1.1
0.60
^C
Charging speed.
cauto_sp
3.9 to 50
24.0
°C
Cooling switching setpoint.
hauto_sp
0 to 46.1
18.0
°C
Heating switching setpoint.
lim_sp1
0 to 100
100
%
Limit setpoint 1
lim_sp2
0 to 100
100
%
Limit setpoint 2
lim_sp3
0 to 100
100
%
Limit setpoint 3
min_sct
26.7 to 55*
40
°C
Condensing setpoint in case of desuperheater use.
* 50, if the unit is equipped with variable speed fan.
INPUT menu
Name
Format
Units
Description
ONOFF_SW
Open/Close
-
Run / Stop remote control.
HC_SW
Open/Close
-
Cooling / heating remote contact.
on_ctrl
Off, On Cool, On Heat, On Auto
-
Current control mode.
SETP_SW
Open/Close
-
Remote setpoint contact.
LIM_SW1
Open/Close
-
Contact 1 for absorption remote limitation.
LIM_SW2
Open/Close
-
Contact 2 for absorption remote limitation.
FLOW_SW
Open/Close
-
Contact detecting water flow / external safety loop.
leak_1_v
nn.n
Volt
Value read by leakage detector 1.
leak_2_v
nn.n
Volt
Value read by leakage detector 2.
DSHTR_SW
Open/Close
-
Contact for the desuperheater available to the user.
OUTPUTS menu
Name
Format
Units
Description
CP_A1
On/Off
-
Compressor A1 output.
CP_A2
On/Off
-
Compressor A2 output.
CP_A3
On/Off
-
Compressor A3 output.
fan_a1
0-2
-
Fan A1 output.
fan_a2
0-2
-
Fan A2 output.
exv_a
0-100
%
Cooling circuit A EXV position.
HD_POS_A
0-100
%
Position of variable flow rate fan regulator A.
RV_A
On/Off
-
Cycle reversal valve status of cooling circuit A.
CP_B1
On/Off
-
Compressor B1 output.
CP_B2
On/Off
-
Compressor B2 output.
fan_b1
0-2
-
Fan B1 output.
exv_a
0-100
%
Cooling circuit B EXV position.
HD_POS_B
0-100
%
Position of variable flow rate fan regulator B.
RV_B
On/Off
-
Cycle reversal valve status of cooling circuit B.
C_HEATER
On/Off
-
Status of heat exchanger heater and of coil lower side.
BOILER
On/Off
-
Heat generator output.
EHS_STEP
0-4
-
Additional electric heater steps
ALARM
On/Off
-
Alarm relay.
RUNNING
On/Off
-
Unit relay ON.