83
PRO-
EN
RUNTIME menu
Name
Format
Units
Description
HR_MACH
nnnnn
hours
Device total operating hours.
st_mach
nnnnn
-
Device total start-ups.
HR_CP_A1
nnnnn
hours
Compressor A1 total operating hours.
st_cp_a1
nnnnn
-
Compressor A1 total start-ups.
HR_CP_A2
nnnnn
hours
Compressor A2 total operating hours.
st_cp_a2
nnnnn
-
Compressor A2 total start-ups.
HR_CP_A3
nnnnn
hours
Compressor A3 total operating hours.
st_cp_a3
nnnnn
-
Compressor A3 total start-ups.
HR_CP_B1
nnnnn
hours
Compressor B1 total operating hours.
st_cp_b1
nnnnn
-
Compressor B1 total start-ups.
HR_CP_B2
nnnnn
hours
Compressor B2 total operating hours.
st_cp_b2
nnnnn
-
Compressor B2 total start-ups.
hr_fana1
nnnnn
hours
Fan A1 total operating hours.
hr_fana2
nnnnn
hours
Fan A2 total operating hours.
hr_fanb1
nnnnn
hours
Fan B1 total operating hours.
st_fa_a1
nnnnn
-
Fan A1 total start-ups.
st_fa_a2
nnnnn
-
Fan A2 total start-ups.
st_fa_b1
nnnnn
-
Fan B1 total start-ups.
hr_cpum1
nnnnn
hours
Pump 1 total operating hours.
hr_cpum2
nnnnn
hours
Pump 2 total operating hours.
nb_def_a
nnnnn
-
Cooling circuit A total defrost cycles.
nb_def_b
nnnnn
-
Cooling circuit B total defrost cycles.
PUMPSTAT menu
Name
Format
Units
Description
CPUMP_1
On/Off
-
Pump 1 control
CPUMP_2
On/Off
-
Pump 2 control
ROT_PUMP
Yes/No n
-
Pump alternation
WATPRES1
±nnn.n
kPa
Water pressure sensor 1
WATPRES2
±nnn.n
kPa
Water pressure sensor 2
WP_CALIB
Yes/No
-
Water pressure sensor temperature?
Due to a fault of the water pressure sensor, WP_OFFST
is automatically deconfigured (-99kPa) to notify the necessity to calibrate the
water circuit. Calibration must be carried out while there is no water circulating
through the device.
WP_OFFST
±nnn.n
kPa
Water pressure sensor calibration value.
DP_FILTR
nnn.n
kPa
Water filter pressure drop.
WP_MIN
nnn.n
kPa
Minimum water pressure.
WAT_FLOW
±nnn.n
g/s
Water flow rate.
CAPPOWER
±nnn.n
kW
Device capacity.
w_dt_spt
nn.n
^C
Temperature jump setpoint.
w_dp_spt
nn.n
kPa
Pressure jump setpoint.
drvp_pwr
+nnn.n
kW
Pump power.
drvp_i
+nnn.n
A
Pump absorption.
drvp_ver
xxxxxxxx
-
Pump speed regulator version.