PRO-
86
EN
BRODCAST menu
Name
Format
Default
Units
Description
ccnbroad
0/1/2
2
-
Broadcast activation
0 = disabled
1= broadcast during holiday, to the network
2= broadcast during holiday, device only.
oatbusnm
0 to 239
0
-
Broadcast of outdoor air temperature
Number of device buses with outdoor air temperature.
oatlocad
0 to 239
0
-
Number of device element with outdoor air temperature.
dayl_sel
Disabled/Enable
Disabled
-
Activation of Summer time / Winter time
Summer time
startmon
1 to 12
3
-
Month.
startdow
1 to 7
7
-
Day of the week (1 = Monday).
startwom
1 to 5
5
-
Week of the month.
Winter time
stopmon
1 to 12
10
-
Month.
stoptdow
1 to 7
7
-
Day of the week (1 = Monday).
stopwom
1 to 5
5
-
Week of the month.
GENCONF menu
Name
Format
Default
Units
Description
lead_cir
0/1/2
0
-
Charging sequence of cooling circuits
0 = automatic
1 = First Circuit A
2 = First Circuit B.
seq_typ
No/Yes
No
-
Charging sequence for the cooling circuit.
ramp_sel
No/Yes
No
-
Charging ramp sequence.
off_on_d
1 to 15
1
min
Starting delay.
nh_limit
0 to 100
100
%
Limitation of the power that can be supplied in night operation mode.
nh_start
00:00 to 24:00
00:00
-
Start time of night operation mode.
nh_end
00:00 to 24:00
00:00
-
End time of night operation mode.
bas_menu
0 to 3
0
-
Basic menu access configuration
0 = full access
1 = access to the Alarm menu with password
2 = access to the Setpoint menu with password
3 = combination of 1 and 2.
synoptic
No/Yes
No
-
Display of synoptic chart
PUMPCONF menu
Name
Format
Default
Units
Description
pump_seq
0/1/2/3/4
0
-
Heat exchanger pump sequence
0 = no pump
1 = one pump
2 = two pumps with automatic switching
3 = manual selection of pump 1
4 = manual selection of pump 2.
pump_del
24 to 3000
48
hours
Interval between pump switching.
pump_per
No/Yes
No
-
Protection against pump mechanical lock.
pump_sby
No/Yes
No
-
Pump stop when device is in stand-by mode.
pump_loc
No/Yes
Yes
-
Water flow rate check when pump is stopped.
HCCONFIG menu
Name
Format
Default
Units
Description
auto_sel
No/Yes
No
-
Automatic switching selection.
cr_sel
0 to 2
0
-
Compensation selection in cooling mode.
hr_sel
0 to 2
0
-
Selection 1 of compensation in heating mode.
1 = according to outside temperature
0 = none
2 = according to temperature difference
heat_th
-20 to 0
-15
°C
Outside temperature threshold for cooling mode.
boil_th
-15 to 15
-10
°C
Outside temperature threshold for heat generator.
ehs_th
-5 to 21.2
5
°C
Outside temperature threshold for additional electric heating.
both_sel
No/Yes
No
-
Heating or cooling control selection for HSM.
ehs_back
No/Yes
No
-
First backup step of the additional electric heating.
ehs_pull
0 to 60
0
minutes
Activation delay of first additional electric heating step.
ehs_defr
No/Yes
No
-
Fast defrost with additional electric heating use.