21
EXAMPLES
1)
To trip self contained siren when the Fire Siren activates:
To have Auxiliary 3 activate for the same time as the Fire Siren on the panel, program the following:
Location 232-235 [0]-[0]-[13]-[0]
2)
To trip self contained siren when the Burglary Siren activates:
To have Auxiliary 4 activate for the same time as Burglary Siren, program the following:
Location 236-239 [0]-[0]-[13]-[1]
3)
To activate external sounder when keypad chimes:
To have Auxiliary 3 follow the “chime” on the keypad, program the following:
Location 232-235 [0]-[0]-[13]-[13]
Note: You must move relay jumpers to set a voltage output (see page 4).
Location 240: Inverting Auxiliary Outputs And Setting Onboard Form C And Form A Relay Operation
(Form C Relay Tied To Pin #3 And Form A Relay Tied To Pin #4)
The auxiliary outputs of the 9000E are normally POSITIVE (+) going NEGATIVE (-). They can be changed to a
normally NEGATIVE (-)going POSITIVE (+) by programming the appropriate number in this location. Auxiliary output
1 has a value of "1", Auxiliary output 2 has a value of "2", Auxiliary output 3 has a value of "4", and Auxiliary output
4 has a value of "8". The values for the outputs that you wish to change to NEGATIVE going POSITIVE must be
added together and the total programmed in this location. For example, if you wished to make outputs 2 (=2) and
3 (=4) NEGATIVE going POSITIVE, you would program "6" (2+4=6) in this location. The output for pin 3 is
automatically tied to the onboard Form C Relay (Terminal locations 34,35, & 36), and pin 4 is tied to the Form A relay
(Terminal locations 38 & 39). You should take this into consideration when planning auxiliary output operation. If
you need a relay output on pins 1 or 2 you must add a relay that can be tripped with the voltage and current available
at these pins. Making outputs 3 and 4 normally negative going positive will have the effect of making the relay
attached to that pin normally pulled in, and drop out when the output is activated. NOTE: THE PINS ARE CURRENT
LIMITED TO 250 MICRO AMPS POSITIVE AND 20 mA NEGATIVE.
Location 241: Changing Timing Increments From Seconds To Minutes For Auxiliary Outputs
The number programmed into this location will determine if the 4 auxiliary pins described in the above locations will
create 2 to 28 second, or 1 to 14 minute voltage trigger outputs. If this location contains a "0" (factory default ="0"),
the output duration time is computed in seconds. By adding the value that corresponds to each pin number in the
table below, and programming the sum in this location, the "second" increments will convert to "minute" increments
for the pin(s) selected:
VALUE
PIN NUMBERS
1
Pin #1
2
Pin #2
4
Pin #3
8
Pin #4
Example 1
- If you need the duration time to change from seconds to
minutes for the trigger output on Pin 1, you would
program a "1" in this location.
Example 2
- If you need the duration time to change from seconds to
minutes for the trigger output on Pin 1 and Pin 3, you
would program a "5" (1 + 4 ="5") in this location.
Example 3
- If you need the duration time to change from seconds to
minutes for the trigger output on Pin 2 and Pin 4, you
would program a "10" (2 + 8 ="10") in this location.