APPENDIX 1
This document describes the 9000E reporting event codes when using the SIA format (format 14). The following
codes are programmable and are sent when the Data 1 location is programmed as the event code. For zones,
programming a "0" as the Data 1 location will result in an automatic selection of the event code depending on the
zone type choosing from Fire, Panic, or Burglary. The Data 2 and Data 3 are then sent as a Zone Identifier.
PROGRAMMED DATA 1
SIA CODE DEFINITION
1
FA
Fire Alarm
2
PA
Panic Alarm
3
BA
Burglary Alarm
4
GA
Gas Alarm
5
KA
Heat Alarm
6
WA
Water Alarm
7
QA
Emergency Alarm
8
SA
Sprinkler Alarm
9
UA
Untyped Alarm
10
HA
Holdup Alarm
11
MA
Medical Alarm
12
ZA
Freeze Alarm
13
TA
Tamper Alarm
14
RP
Periodic Test
15
Reserved
The following event codes are fixed, but must be enabled by programming a 1 in the corresponding location.
REPORTING EVENT
SIA CODE
PROGRAMMING LOCATION
Keypad Tamper
TA
336
Autotest
RP
340
Opening
OP
348
Closing
CL
350
Cancel
OC
354
AC Loss
AT
356
Low Battery
YT
360
Restore Code
*R
364
Bypass Code
*B
368
Bypass Restore
*U 368 / 364
Trouble Code
*T
372
Trouble Restore
*R 372 / 364
AC Restore
AR
376
Battery Restore
YR
376
Expander Trouble
ET
378
Expander Trouble Restorer
ER
511
Fail to Close
CL
592
Early Opening
OK
588
Download Complete
RS
596
RF Loss of Supervision
ET (For these two - see
RF Sensor Low Battery
XT 9090 Installation Manual)
* The character transmitted in this slot will be the first character in the SIA code from the top list for the event
being reported. If a "1" is programmed in location 364, and a Burglary Alarm (BA) restores, a BA will be
transmitted. If a "1" is programmed in location 372, and a Fire Alarm (FA) zone goes into Trouble, an (FT) will
be transmitted.