Location 214: Smoke Power Reset And/Or Fire Alarm Verification
Programming a "1" in location 214 will cause the 9000E (when in the disarmed state) to interrupt the smoke detector
power each time the [#] button is pressed. If this location contains a "0", the smoke detector power will reset only
after the [#] button is pressed when the corresponding LED(s) for zones designated as "Priority" are on steady for
alarm or blinking for trouble. Programming a "2" in this location will enable the "Fire Alarm Verification" feature. When
the "Fire Alarm Verification" feature is enabled, a smoke detector will be powered down and reset automatically after
the first trip, waiting for a second trip within a 2 minute time frame (thus verifying a fire alarm condition) before
creating an alarm and communicating a message. Program a “3" to enable both of these features. Factory default
is “1" and this feature is enabled.
Location 215: Siren Output Limit
If a "1" is programmed in location 215, the siren output will only activate once per zone during each arming cycle.
Factory default is "0" and this feature is disabled.
Location 216: Communicator Report Limit
If a "1" is programmed in location 216, the communicator will only report once per zone during each arming cycle.
Factory default is "0" and this feature is not enabled.
Location 217: Partition Siren Inhibit
Factory default is "0" and this feature is disabled, meaning a valid code entered from a keypad in any partition will
silence the siren regardless of what partition caused the alarm. If a "1" is programmed in this location, only the
keypad within the partition which caused an alarm can silence the siren.
Location 218: European Pulse Dial Ratio
Programming a "1" in this location will change the internal clock to accept 50 Hz power. Programming a "2" in this
location will provide a European pulse dial ratio. Programming a "3" in this location will provide both. Factory
default is "0", disabling this feature.
Location 219: Enabling The Swinger Shutdown
Location 219 is used to enable the burglary zone swinger shutdown. The number programmed in this location will
determine the number of trips the Ranger 9000E will allow before bypassing all burglary zones (1-16) which have
tripped during an arming cycle. The bypassed zones will not report trips to a central station, and the local siren or
bell will not sound for these zones. A zone trip will not be added to the number count until after the zone has tripped
more than once. A zone trip will only be added each time the siren cycle starts. If this location contains a "0", this
feature is disabled. A zone which has been bypassed by this feature will be reported if
Bypass Reporting
is
enabled.
NOTES: 1) Programming Location 215 will disable swinger shutdown. 2) If "Immediate Restore
By Zone" is enabled in location 204, multiple reports may be transmitted during a siren cycle without adding
to the trip count.