5
TERMINAL DESCRIPTION
TERMINAL #
DESCRIPTION
1
Connect one side of zone 1 loop. Connect other side of loop to common terminal 2. Open
or short causes alarm.
2
Common (-) Terminal.
3
Connect one side of zone 2 loop. Connect other side of loop to common terminal 2. Open
or short causes alarm.
4 - 12
See Terminal Drawing and repeat the above sequence for zones 3 through 8.
13 - 14
Auxiliary power, regulated 12VDC, maximum 1 AMP.
15 - 26
See Terminal Drawing and continue above described hookup zones 9 through 16.
27 - 28
Auxiliary power, regulated 12VDC, maximum 1 AMP .
29
Earth Ground, connect to a cold water pipe, or 6 to 10 foot driven rod.
30 - 31
AC input, connect a 16.5V 50VA, Class II U.L. approved transformer (included).
32 - 33
Resettable 12VDC 250mA Aux power.(Memory reset and/or Smoke detector power)
34 -36
Form C programmable on board relay output. Tied to auxiliary output #3.
37
Negative, provided as a convenience for relay connection.
38 - 39
Form A programmable on board relay output. Tied to auxiliary output #4.
40 - 41
Siren driver output to speaker(s). Min speaker rating 30/40 watt at 4, 8, or 16 ohms .
42 - 45
Connect keypad wires as follows; Green to terminal 42, Yellow to terminal 43, Red to
terminal 44, and Black to terminal 45. Maximum run with 22 gauge wire is 200ft, maximum
run with 18 gauge wire is 500ft. Home run cable to each keypad.
T1
House Telephone Tip (Brown).
T
Telephone Tip (Green).
R
Telephone Ring (Red).
R1
House Telephone Ring (Gray).
Battery Leads
Connect to 12VDC lead acid rechargeable battery: Black(-) & Red(+). Do not use a dry cell
battery.
FUSE DESCRIPTION
FUSE #
DESCRIPTION
F1
2 AMP / Auxiliary Power.
F2
3 AMP / Auxiliary Outputs 3 & 4.
F3
3 AMP / Siren Driver.
F4
1 AMP / Keypad and Smoke Detector Power.