Locations 620-621: Autotest Report Intervals
Locations 620 and 621 contain the number of days in the autotest report intervals. Location 620 is the tens (10's)
digit, and location 621 is the ones (1's) digit. The available interval is 1 to 99 days. If a 1 to 9 day interval is selected
the first location should remain a zero "0". If the selected interval is every 75 days, you would program a "7" in
location 620 and a "5" in location 621. Locations 340-342 must be programmed to enable autotest reporting.
Location 622: Automatic Download Callback Enable/Autotest Suppression
Programming a "1" in location 622 will cause the control panel to automatically call the download computer callback
number at every autotest interval. This feature will not activate unless a callback phone number has been
programmed, and a "2" is programmed in location 660. If a "2" is programmed in location 622, the autotest report
will be suppressed, if the communicator has sent any report since the last autotest. To enable both features,
program a “3" in this location. Factory default is “0".
Location 623: AC Power Loss Delay Feature
The number programmed in location 623 represents the number of 1 minute increments the
AC Power Loss
report
is delayed before a communication is initiated, from 1 to 15 minutes. Factory default is "5" programmed in this
location and
AC Power Loss
reports will be delayed 5 minutes. If a "0" is programmed in this location this feature
is not enabled. The
AC Power Restore
, if enabled in location 376, will also delay reporting until after the number
of minutes programmed in this location has elapsed.
Location 624-625: Programming The Number Of Elapsed Days Since Last Auto Test Report
Location 624 contains the tens digit of the number of days between autotest reports and location 625 contains the
ones digit. Example: If today is Thursday, and you want a weekly test on Sundays (a "0 - 7" in locations 620-621),
program a "0" in location 624, and a "4" in location 625 (four days have elapsed).
Location 626: Programming Current Day Of Week
A number from 1 to 7 should be programmed in this location to indicate the current day of the week. Program a “2"
in this location for a Monday. If the day is Friday, program a "6" in this location. Sunday ="1" and Saturday ="7".
Location 627: Programming The Current Month
Location 627 contains the current month. The month must be programmed using a number from "1" to "12".
Location 628: Programming The Current Day Of Month - Tens Digit
Location 628 should be programmed with first digit of the current day of the month. If the current date is December
25th, program a "2" in location 628.
Location 629: Programming The Current Day Of Month - Ones Digit
Location 629 should be programmed with the second digit of the current day of the month. If the current date is
December 25th, program a "5" in location 629.
Location 630: Programming The Current Year - Tens Digit
Location 630 contains the current year - tens digit. If the current year is 1996, this location should contain a 9, which