![RADWAG PUE HY10 Скачать руководство пользователя страница 116](http://html2.mh-extra.com/html/radwag/pue-hy10/pue-hy10_user-manual_3388032116.webp)
116
The condition is marked with signal flags, which determine formulation making
process between the weighing platforms, in a way which orders dosing Water
ingredient as the second one. The whole process is described below in
tables, separately for each weighing platform.
Dosing process name:
Instance 2
Dosing process code:
2222
Dosing process from an indicator level:
Platform 1
Icon
Step
Value
Description
1. [CM] Weight
condition
Gross<0.1 kg
Condition checking, unless the weighing
platform is loaded with a mass exceeding
100 g
2. [Z] Zero
Zero
Zeroing the weighing platform no. 1
3. [TI] Delay
[5s] Open
valve Flour
Pending for opening main valve of the
container with “Flour”
4. [DA] Automatic
batching
1,2 kg [Flour]
Automatic dosing of product „Flour” to
obtain 1 kg mass in bulk dosing mode
(bulk dosing and fine dosing valves are
opened – Outputs 1 and 2), and 0,2 kg
mass is dosed using fine dosing valve only
–fine dosing valve is opened on Output 1
(for two-step dosing process)
5. [TI] Delay
[3s] Close
valve „Flour ”
Pending for closing the main valve of the
container “Flour”
6. [O] Outputs
Output 11 – „1”
Output 11 takes high status („1”) – signal
confirming carrying out the dosing making
process on the weighing platform no. 1 is
lit up
7. [F] Set flags
Signal flag 1 –
„1”
Setting the characteristic point of the
process, which is a condition for carrying
out part of the process on the second
weighing platform
Dosing on the first weighing platform is carried out in two-steps, as for
ingredient „Flour” the outputs are set for two-step dosing – see Products
database.
Содержание PUE HY10
Страница 1: ...USER MANUAL ITKU 88 03 08 17 EN PUE HY10 WEIGHING INDICATOR www radwag com...
Страница 2: ...2 AUGUST 2017...
Страница 13: ...13 5 WEIGHING INDICATOR STRUCTURE 5 1 External view 5 2 Main dimensions PUE HY 10 indicator dimensions...
Страница 248: ...248 Fig 21 12IN 12OUT 40 1 2 12IN OUT schematic diagrams 12 inputs 12 outputs...
Страница 268: ...268 Indicator printer CITIZEN EPSON cable Indicator ZEBRA printer cable Indicator IN OUT cable...
Страница 271: ...271 45 ERROR MESSAGES...
Страница 305: ...305...