A3410
1
2
3
4
I
III
II
Fig. 5: Cable assignment at the terminal box of the DULCO turb C
I. Mains cable threaded connector (supplied
without a mains cable). The threaded connectors
are suitable for cable diameters of 5.8 mm (0.230
in) to 10 mm (0.395 in.)
II. Alarm cable threaded connector
III. Sensor cable threaded connector
1. Alarm terminal 1 and 2 (0.25 ... 1.5 mm
2
) max‐
imum 2 A
2. Terminal 4 ... 20 mA / RS-485 (0.25 ... 1.5 mm
2
)
3. Terminal box
4. Mains cable terminal (0.25 ... 1.5 mm
2
)
Assembly and installation
20