Configure the Module
6202-WA-DFNT-DFCM3
♦
ProLinx Gateway
Wireless EtherNet/IP to DF1 Master/Slave-3 ports
ProSoft Technology, Inc.
Page 37 of 190
February 2, 2009
Parameter Range
Description
Swap Code
0,1,2,3
This parameter defines if the data received from the Server is to
be ordered differently than that received from the Server device.
This parameter is helpful when dealing with floating-point or other
multi-register values, as there is no standard method of storage of
these data types in Server devices. This parameter can be set to
order the register data received in an order useful by other
applications. The following table defines the values and their
associated operations:
Swap Code
Description
0
None - No Change is made in the byte
ordering (1234 = 1234)
1
Words - The words are swapped
(1234=3412)
2
Words & Bytes - The words are swapped
then the bytes in each word are swapped
(1234=4321)
3
Bytes - The bytes in each word are
swapped (1234=2143)
The words should be swapped only when using an even number
of words.
Node IP
Address
xxx.xxx.xxx.xxx
The IP address of the device being addressed by the command.
Slot
Use a value of -1 when interfacing to an SLC 5/05 or a SLC5.
These devices do not have a slot parameter. When addressing a
ControlLogix processor, the slot number corresponds to the slot in
the rack containing the controller being addressed. In the
ControlLogix platform, the controller can be placed in any slot and
the rack may contain multiple processors. This parameter uniquely
selects a controller in the rack.
Function
Code
See Command Function Codes
(page 35, page 117)
These parameters specify the function to be executed by the
command. The Reference chapter in this manual describes the
meaning of these values for each of the available supported
commands. Following is a complete list of the command
supported by the Client driver.
Function Code Listing
Basic Command Set
1
Protected Write
2
Unprotected Read
3
Protected Bit Write
4
Unprotected Bit Write
5
Unprotected Write
PLC-5 Command Set (0x0F)
100
Word Range Write (Binary Address)
101
Word Range Read (Binary Address)
102
Read-Modify-Write (Binary Address)
150
Word Range Write (ASCII Address)
151
Word Range Read (ASCII Address)
152
Read-Modify-Write (ASCII Address)
SLC Command Set (0x0F)
501
Prot Typed Read with 2 addr fields
502
Prot Typed Read with 3 addr fields
509
Prot Typed Write with 2 addr fields
510
Prot Typed Write with 3 addr fields
511
Prot Type Write with Mask 3 addr field
Function
Parameters
See Command Function Codes
(page 35, page 117)
The number of auxiliary parameters required is dependent on the
function code selected for the command.