Configure the Module
6202-WA-DFNT-DFCM3
♦
ProLinx Gateway
Wireless EtherNet/IP to DF1 Master/Slave-3 ports
ProSoft Technology, Inc.
Page 51 of 190
February 2, 2009
#
# SWAP CODE
DEFINITION
0 Bytes left in original order (1234 -> 1234)
1 Words are swapped (1234 -> 3412)
2 Words and bytes are swapped (1234 -> 4321)
3 Bytes in each word are swapped (1234 -> 2143)
[DATA MAP]
# From To Register Swap Delay
# Address Address Count Code Preset
START
4000 1000 9 0 1000
4170 1010 2 0 1001
4370 1020 30 0 1002
6300 1100 20 0 1003
END
From Address
0 to highest Status Data address
This field specifies the internal database register to copy from. This address can
range from the Data area as well as the Status Data Area of the product
To Address
0 to 3999
The destination for the copy is always within the Register Data area.
Register Count
1 to 100
This parameter specifies the number of registers to copy.
Swap Code
0,1,2,3
You may need to swap the order of the bytes in the registers during the copy
process in order to change from alignment of bytes between dissimilar protocols.
This parameter is helpful when dealing with floating-point or other multi-register
values, as there is no standard method of storage of these data types in slave
devices.