AW-I - Manual
|
priceindustries.com
AW-I
APPENDICES
FIGURE 7: HIGH VOLTAGE WIRES SPOOLED
12. All high voltage wiring (such as fans,
motors, blowers, compressors, etc.)
is spooled by the factory and is to
be pulled through the air handler
unit upon assembly (Figure 7).
Wires should be connected to the
corresponding labeled terminals.
13. All low voltage control wiring (such
as actuators, sensors, etc) is
disconnected at the air handler unit
splits. Spade connectors or junction
boxes containing terminal blocks
are installed at the splits. All control
wiring and terminals are marked to
aid with on-site assembly.
14. The unit is now ready to be
connected to the main power
source. This operation must be
performed by a qualified electrician
and done according to local codes
and regulations.