An optional space thermostat or sensor may be shipped loose
for field installation. The sensor may be duct mounted and/or
wall mounted.
1. Locate space sensors or thermostats where they will
provide a representative reading of the space condition.
2. Avoid areas with cold drafts or in the warm supply-air
stream of the unit.
3. On indoor units, do not mount the thermostat or sensor on
the unit casing, as it may be affected by heat radiating off
the unit.
4. Do not place near other sources of warmth, such as
lamps, appliances, etc.
5. Refer to unit electrical wiring diagrams for details on how
to wire the sensor to the control panel.
6. Ensure that all remote wiring is equivalent to factory
installed wiring and that voltage drop does not exceed 10
percent.
An optional duct mounted discharge air temperature sensor
may be shipped loose for field installation.
1. The sensor strip must be parallel to the flow of air.
2. The sensor must be mounted as close to the center of the
duct as possible.
3. The sensor must be located in a straight section of the
duct and must be 8-10 feet (2.4 to 3m) downstream from
the supply air connection.
4. Do not install temperature sensors near any elbows or
transitions.
5. Refer to unit electrical wiring diagrams for details on how
to wire the sensor to the control panel.
6. Ensure that all remote wiring is equivalent to factory
installed wiring and that voltage drop does not exceed 10
percent.
TYPICAL DUCT MOUNTED TEMP. SENSOR
TYPICAL SPACE SENSOR
11
AW-I
INSTALLATION INSTRUCTIONS