Draw Through Trap Sizing
H1 = Supply Fan TSP + 1 inch (2.5cm)
H2 = 0.5 x H1
Example:
Size a condensate trap for a unit with TSP of 5 in (12.5 cm)
w.c.
H1 = 5 + 1 = 6 inches (15 cm)
H2 = 0.5 x 6 = 3 inches (7.5 cm)
Blow Through Trap Sizing
H1 = supply fan TSP + 1 inch (2.5 cm)
H2 = H1 - ½ inch (1.3 cm)
Example:
Size a condensate trap for a unit with TSP of 5 in (12.5 cm)
w.c.
H1 = 5 + 1 = 6 inches (15 cm)
H2 = 6 – 1/2 = 5 1/2 inches (14 cm)
Wash Down Drains
Some units may be supplied with wash-down drains. These
allow water to drain from a periodical wash-down of the
inside of the unit. It is not recommended to trap these drain
connections. While it will not damage the unit, the traps would
need to be constantly primed to provide a seal. The following
are acceptable options:
1. Provide caps for each wash-down drain. These can be
removed during the wash-down process and a hose can
be attached to direct flow to a suitable floor drain (indoor
applications).
2. Pipe all the wash-down drains to a suitable floor drain
(indoor applications) and include a shut-off valve. The
valve can be opened during the wash-down process.
COOLING COIL CONDENSATE TRAP
WASH-DOWN DRAIN CONNECTION
16
AW-I
INSTALLATION INSTRUCTIONS
AW-I - Manual
|