TYPICAL REMOTE CONTROL PANEL
An optional remote control panel may be shipped loose for
field installation.
1. Locate the panel indoors where operations and
maintenance personnel have ready access.
2. Refer to unit electrical wiring diagrams for details on how
to wire the sensor to the control panel.
3. Ensure that all remote wiring is equivalent to factory
installed wiring and that voltage drop does not exceed 10
percent.
Where possible, the low limit temperature sensor is factory
mounted. Some unit configurations require the sensor to be
field mounted in the supply air ductwork. In this situation, the
sensor and field wiring will be coiled up in the weather housing.
The installing contractor shall install the sensor approximately
10 ft. (3 m) down the supply air duct.
12
AW-I
INSTALLATION INSTRUCTIONS
AW-I - Manual
|
priceindustries.com