29
Jumper Settings
The Controller Outputs (Output-1, Output-2 & Output-3) can be configured for different types (Relay, SSR, DC Volts & DC
Current) that require jumper settings besides appropriate parameter settings. The jumper settings are provided in the form of
Pins & Shorting-Link arrangements as depicted in figures 10.5 below.
User Manual
neuro 102 Plus
Figure 10.5 : Jumper Settings
Pins Shorted
(b)
Link Parked
(c)
Pins
Shorting
Link
(a)
OUTPUT-1 Configuration
The Output-1 circuit is assembled on CPU PCB itself with 2 jumper setting arrangements as shown in figure 10.6 below. Refer
Table 10.1 for jumper setting arrangement to select different output type.
Table 10.1 : Output-1 Jumper Settings
Relay
SSR Drive
DC Linear
Current
(or Voltage)
Jumper Settings
Shorting Link
A
: Short Pins A1 & A4
Shorting Link
B
: Park
Shorting Link
A
: Short Pins A3 & A4
Shorting Link
B
: Short Pins B1 & B2
Shorting Link
A
: Short Pins A2 & A3
Shorting Link
B
: Short Pins B2 & B3
Output Type
Figure 10.6
A1
A4
A3
A2
B1
B2
B3