10
Refer Table 4.1 for the parameter descriptions and settings.
CONTROL PARAMETERS : PAGE-10
Table 4.1
0 to 600 Seconds
(Default : 16 sec.)
0 to 3600 Seconds
(Default : 100 sec.)
Parameter Description
Settings
(Default Value)
PROPORTIONAL BAND
(Available for PID Control only)
Sets proportional gain (% power per unit error). Defined in same
units and resolution as that for PV.
INTEGRAL TIME
(Available for PID Control only)
Sets integral time constant in seconds. Setting the value to 0, cuts-
off integral action.
DERIVATIVE TIME
(Available for PID Control only)
Sets derivative time constant in seconds. Setting the value to 0,
cuts-off derivative action.
0.5 to 100.0 Seconds
(in steps of 0.5 secs.)
(Default : 10.0 sec.)
CYCLE TIME
(Available for PID Control only)
Sets the total ‘On + Off’ time in seconds for time modulating power
output through Output-1 Relay / SSR.
0.1 to 10.0
(Default : 1.0)
RELATIVE COOL GAIN
(Available for PID Control with bi-directional, that is, Heat-
Cool mode)
Sets the ratio of cooling power to the heating power.
COOL CYCLE TIME
(Available for PID Control with bi-directional, that is, Heat-
Cool mode)
Sets the On + Off cycle time in seconds for time modulating power
output through Output-2 Relay / SSR.
0.5 to 100.0 Seconds
(in steps of 0.5 secs.)
(Default : 10.0 sec.)
HYSTERESIS
(Available for On-Off or Pulsed On-Off Control only)
Sets differential (dead) band between On-Off switching for
Output-1. Defined in same units and resolution as that for PV.
PULSE TIME
(Available for Pulsed On-Off Control only)
Sets the total ‘On + Off’ pulse time in seconds for Output-1 Relay /
SSR output.
Pulse ON Time
to 120.0 Seconds
(Default : 2.0 sec.)
User Manual
neuro 102 Plus
Section 4
1 to 9999 counts
(Default : 500)
1 to 9999 counts
(Default : 2)