19
Note : This Section is applicable only if the Controller is supplied with “Setpoint Profile” option.
The profile utility requires profile configuration and profile settings. Also, the controller facilitates on-line alterations of the
parameters pertaining to the running segment. To simplify profile operation, the rather large list of parameters has been split in
multiple pages as under.
Profile Configuration : PAGE-16
Use this list of parameters to configure the profile for number of segments, number of cycles (repeats), output(s) status upon
profile completion and power fail recovery method. Refer Table 8.1 below.
PROFILE PARAMETERS : PAGE-16, PAGE-14, PAGE-1
User Manual
neuro 102 Plus
Table 8.1
Settings
(Default Value)
Parameter Description
1 to 9999
(Default : 1)
1 to 16
(Default : 16)
PROFILE MODE ENABLE
Enable or Disable the setpoint profile feature. If disabled, all the
profile related parameters and commands are suppressed.
NUMBER OF SEGMENTS
Set the number of segments to constitute the setpoint profile.
Set the number of times the profile is to be repeated (cycled)
before end of profile. After completion of the last segment of the
running profile cycle, the profile restarts from the first segment.
NUMBER OF REPEATS
COMMON HOLDBACK
The profile allows either
Common
or
Independent
‘Holdback Type’
and ‘Holdback Value’ for all profile segments. Set this parameter
to ‘Yes’ if common settings are desired for the Holdback feature.
(Default : Yes)
No
Yes
(Default : Disable)
Disable
Enable
Section 8
(Default : Continue)
Abort
Continue
OUTPUT OFF
Set to ‘Yes’ if after the end of profile, all the control outputs are to be
forced Off
till the issuance of next profile Start command.
POWER FAIL STRATEGY
Selecting
Abort
terminates a running profile in case of power
failure.
Selecting
Continue
resumes :
(a) The ramp segment execution with the profile setpoint
prevailing at the time of power failure.
(b) The soak segment execution for the balance time.
(Default : No)
No
Yes