15
PV RESOLUTION
(Available for DC linear mV/V/mA & RTD Inputs only)
Set the process value indication resolution (decimal point). All the
resolution based parameters (Control Setpoint, Hysteresis, Alarm
Setpoints etc.) then follow this resolution setting.
PV RANGE LOW
(Available for DC Linear Inputs)
Set process value corresponding to SIGNAL LOW parameter
value. Refer
Appendix-A : DC Linear Signal Interface
for details.
PV RANGE HIGH
(Available for DC Linear Inputs)
Set process value corresponding to SIGNAL HIGH parameter
value. Refer
Appendix-A : DC Linear Signal Interface
for details.
Parameter Description
Settings
(Default Value)
OFFSET FOR PV
This value is algebraically added to the measured PV to derive the
final PV that is displayed and compared for alarm / control.
Final PV = Measured PV + Offset
0.5 to 60.0 Seconds
(in steps of 0.5 Seconds)
(Default : 2.0 sec.)
DIGITAL FILTER TIME CONSTANT
Set the time constant, in seconds, for the low-pass digital filter
applied to the measured PV. The filter helps smoothing/averaging
the signal input and removing the undesired noise.
User Manual
neuro 102 Plus
SIGNAL HIGH
(Available for DC linear mV/V/mA Inputs only)
The transmitter output signal value corresponding to PV RANGE
HIGH parameter value. Refer
Appendix-A : DC Linear Signal
Interface
for details.
Input Type
Settings
Default
0 to 20 mA
4 to 20 mA
0 to 80 mV
Reserved
0 to 1.25 V
0 to 5 V
0 to 10 V
1 to 5 V
Signal Low to 20.00
20.00
20.00
80.00
80.00
1.250
5.000
10.00
5.000
Signal Low to 20.00
Signal Low to 80.00
Signal Low to 80.00
Signal Low to 1.250
Signal Low to 5.000
Signal Low to 10.00
Signal Low to 5.000
Refer Table 6.2
(Default : 1)
-1999 to 9999
(Default : 0)
-1999 to 9999
(Default : 1000)
For DC mA/mV/V
:
1 to 9999 counts
For Thermocouples/RTD
:
1 to 999 or 0.1 to 999.9
(Default : 0)