21
SEGMENT SKIP COMMAND
Use this command to terminate a running profile segment and to
move to the next segment. Skipping the last segment will result in
completion of the current profile cycle.
PROFILE PAUSE COMMAND
This parameter is available while a profile cycle is in progress and
can be used to Pause (halt) the profile as long as desired. Set the
command to ‘Yes’ for Pausing and ‘No’ to continue. Under Pause
state, the ramp segment stops ramping while the soak segment
stops counting down the timer.
PROFILE ABORT COMMAND
These parameters are mutually exclusive. Use
Start
command to
commence a new profile cycle and
Abort
command to abort /
terminate a running profile cycle. Set the value to ‘Yes’ to issue the
command.
PROFILE START COMMAND
Parameter Description
Settings
(Default Value)
No
Yes
(Default : No)
No
Yes
(Default : No)
No
Yes
(Default : No)
SEGMENT HOLDBACK TYPE
The modified Holdback Band Type is applied immediately on the
current segment.
SEGMENT TIME INTERVAL
The time interval for a
Ramp
segment actually determines the
RATE at which the setpoint steps towards the target setpoint.
Thus, altering the time interval shall immediately affect the ‘Ramp
Rate’ for the current segment.
If the time interval is modified for the
Soak
segment then the time
elapsed so far is ignored and the soak timer starts counting down
to 0 from the altered time interval value.
User Manual
neuro 102 Plus
None
Up
Down
Both
END OF PROFILE ACKNOWLEDGE
This parameter is available if Output-2 and / or Output-3 Relay /
SSR is programmed to turn ON as an ‘End Of Profile’ signal. Set
this parameter to ‘Yes’ (after end of profile is reached) to
acknowledge the alarm and to turn OFF the output.
No
Yes
(Default : No)
The following parameters allow altering the running segment values (Time Interval, Holdback
Band Type & Holdback Band Value) and Number of Repeats. The alterations made on the running
segment are applicable only for the current execution of the profile cycle.
0 to 9999 Minutes
Table 8.3