SUPERVISORY PARAMETERS : PAGE-13
Refer Table 7.1 for parameter description & settings.
Table 7.1
Settings
(Default Value)
SELF-TUNE COMMAND
(Available for PID control only)
Set to ‘Yes’ to initiate a new tuning cycle or set to ‘No’ to abort a
tuning operation in progress.
Parameter Description
OVERSHOOT INHIBIT
(Available for PID control only)
Enabling this feature controls the rate of PV rise or fall upon
process start-up in order to reach the control setpoint with
minimum overshoot/undershoot possible.
1.0 to 2.0
(Default : 1.0)
OVERSHOOT INHIBIT FACTOR
(Available for PID control with Overshoot Inhibit enabled)
This parameter adjusts the effectiveness of the Overshoot Inhibit
feature. Increase the value if the overshoot is curbed but the PV
takes longer to reach the SP. Decreases the value if the overshoot
persists.
(Default : Disable)
Disable
Enable
(Default : No)
No
Yes
MANUAL MODE
Supervisory permission for Auto/Manual mode selection. Set to
‘Enable’ for permission.
SP ADJUSTMENT ON OPERATOR PAGE
Supervisory permission for control setpoint editing on Operator
Page. Set to ‘Enable’ for permission.
SP ADJUSTMENT ON LOWER READOUT
Supervisory permission for control setpoint editing on Lower
Readout. Set to ‘Enable’ for permission.
ALARM SP ADJUSTMENT
ON OPERATOR PAGE
Supervisory permission for Alarm setpoint adjustments on
Operator Page. Set to ‘Enable’ for permission.
STANDBY MODE
Supervisory control over availability of Standby (entry / exit)
command on Operator Page. ‘Enable’ for availability.
(Default : Enable)
Disable
Enable
(Default : Enable)
Disable
Enable
(Default : Disable)
Disable
Enable
(Default : Disable)
Disable
Enable
(Default : Disable)
Disable
Enable