30
User Manual
neuro 102 Plus
Output-2 & Output-3 Relay / SSR Module Configuration
The output-2 & output-3 Relay / SSR Modules can be configured for either Relay output or SSR output by appropriate Jumper
Settings. Refer Figure 10.7 & Table 10.2 below.
Figure 10.7
Relay/SSR Module
(Output-2 / Output-3)
A1
A2
A3
A4
A5
A6
Table 10.2
Relay
SSR
Output Type
Jumper Setting
(Used 2 Short Links)
Short pins A2 & A3
and
Short pins A5 & A6
Short pins A1 & A2
and
Short pins A4 & A5
Output-2 & Output-3 DC Linear Voltage / Current Modules
The DC Linear Module is factory configured for either Current or Voltage output. The current output can be configured for 0-20
mA or 4-20 mA and similarly the voltage output can be configured for 0-5 V or 0-10 V through parameter settings. No Jumper
Settings are required.
Serial Communication or Auxiliary SP Selection PLUG-IN MODULES
The plug for the Serial Communication or Auxiliary SP Selection module is located on the Power-supply PCB. The Figure 10.8
below illustrates how to plug-in the Serial Communication/Auxiliary SP module. To plug (or unplug) the module simply insert
(or remove) the socket into (or from) the plug. Refer Figure 10.8 below.
Figure 10.8
Mounting Serial Communication/Auxiliary SP Selection Module
Main Board
RS485 Male Connector (Plug)
on Main Board
Serial Communication or
Module
Auxiliary SP Selection
Female Connector (Socket)