Use and installation manual
Page
84
of
97
(PVI-10.0/12.0-I-OUTD(-S)-400 Rev:1.3)
RJ45 connectors
Pin
#
Signal
Name
Description
1
Not Used
2
Not Used
3
+TR
+ Data Line
RS485 communication
4
+R
Remote OFF
Remote control (see chapter 5.5.6.10 for
details).
5
-TR
- Data Line
RS485 communication
6
Not Used
7
RTN
Signal Return
Common ground for logical signals
8
Not Used
6.1.3
Daisy chain
The RS-485 terminal block or RJ45 connectors can be used to connect a single
AURORA inverter or multiple inverters connected in a daisy chain. The maximum
number of inverters that may be connection in a daisy chain is 62. The recommended
maximum length of this chain is 1000 meters.
If several inverters are connected in a daisy chain, it will be necessary to assign an address
to each. See paragraph 5.5.6.1 for information on changing addresses.
Furthermore, the last inverter in the chain must have the line termination contact activated
(switch S2 -120
Ω
TERM in ON position). See Fig
.
25.
Each AURORA is provided with default address two (2), and with the S2 switch in OFF
position.
In order to ensure optimum communication on the RS485 line, Power-One recommends
connecting the PVI-USB-RS485_232 adaptor between the first unit of the daisy chain
and the computer. See Fig. 26 for details. (RS485-USB Convertor)
Содержание Aurora PVI-10.0-I-OUTD-400
Страница 46: ...Use and installation manual Page 45 of 97 PVI 10 0 12 0 I OUTD S 400 Rev 1 3 Fig 19 Data Transmission Options ...
Страница 99: ...AURORA Inverter Fotovoltaici MANUALE INSTALLAZIONE E OPERATORE Model number PVI 10 0 12 0 I OUTD S 400 Rev 1 3 ...
Страница 143: ...Manuale d uso e installazione Pagina 45 di 97 PVI 10 0 12 0 I OUTD S 400 Rev 1 3 Fig 19 Data Transmission Options ...
Страница 196: ...AURORA Photovoltaik Wechselrichter INSTALLATIONS UND BEDIENUNGSHANDBUCH Model number PVI 10 0 12 0 I OUTD S 400 Rev 1 3 ...