Use and installation manual
Page
73
of
97
(PVI-10.0/12.0-I-OUTD(-S)-400 Rev:1.3)
5.5.6.11
Remote Control
This control is used to enable / disable the inverter remote switch-off function by
using the correct control signal (on the signal terminal box):
Fig. 23 – Remote signal terminal box OFF (+R / -R)
If you choose to enable this option, it will be possible to control AURORA
ON/OFF by connecting a relay contact or switch between the two coR and
–R.
Disable: AURORA operation is automatic, based on the radiation
conditions (and grid presence) and is not influenced by the condition of
the control contact
Enable: by closing the contact bR and –R, AURORA is forced
into shut-down. The state of the control signal can be read from the
internal microprocessor and, if closed, the display shows the state of
forced OFF:
Waiting Rem.ON…
to restart
Remote OFF
Remote ON/OFF
Disable
Remote ON/OFF
Enable