5.5.6.12
UV Prot.time
Using this function it is possible to set the length of time for which the inverter will
remain connected, after input voltage drops below the Under Voltage limit fixed at
70% of Vstart value.
For example, having set the UV Prot.time at 60 seconds, if Vin voltage drops
below 90V at 09.00, the inverter will remain connected to the grid (at 0 power)
until 09.01.
The default setting is 60 seconds. The user may change this setting from 1 to 3,600
seconds.
5.5.6.13
MPPT
This function is used in order to set the parameters for the Maximum Power Point
Tracker function.
MPPT Amplitude: this setting allows you to choose the amplitude of disturbance
introduced in DC in order to establish the optimal work point. There are three
choices (LOW, MEDIUM, HIGH). The default setting is MEDIUM.
You can enable the scan function to identify the maximum multiples.
The time can be set every time the system starts a maximum multiples scan. The
default setting is 15 minutes.
You may also decide to perform a manual scan, by using the specific control.
Manual Scan
Scan Interval
15 min
Scan En/Dis
Scan Interval
MPPT Amplitude
Multi-Max Scan
MPPT Amplitude
LOW
MPPT Amplitude
Multi-Max Scan
T Potez. UV
60 secs
Содержание Aurora PVI-10.0-I-OUTD-400
Страница 46: ...Use and installation manual Page 45 of 97 PVI 10 0 12 0 I OUTD S 400 Rev 1 3 Fig 19 Data Transmission Options ...
Страница 99: ...AURORA Inverter Fotovoltaici MANUALE INSTALLAZIONE E OPERATORE Model number PVI 10 0 12 0 I OUTD S 400 Rev 1 3 ...
Страница 143: ...Manuale d uso e installazione Pagina 45 di 97 PVI 10 0 12 0 I OUTD S 400 Rev 1 3 Fig 19 Data Transmission Options ...
Страница 196: ...AURORA Photovoltaik Wechselrichter INSTALLATIONS UND BEDIENUNGSHANDBUCH Model number PVI 10 0 12 0 I OUTD S 400 Rev 1 3 ...