8.3
General characteristics
Description
Value
PVI-10.0-I
Value
PVI-12.0-I
Maximum efficiency
97.3%
97.3%
Internal consumption
in stand-by mode
< 8 W
Internal consumption
at night
< 2 W
Operating ambient
temperature
from -25°C to +60°C (*)
Level of casing
protection
IP65 / Nema 4X
Environmental
category
For outdoor use (Outdoor)
Pollution degree
3
Overvoltage
category
(in
compliance with IEC
62109-1)
II (Input DC circuit)
III (Output AC circuit)
Audible noise when
internal fan is
operating
< 50 dbA @ 1m
Size (height x width
x depth):
716 x 645 x 222 mm
Weight
45 kg
Relative humidity
0 – 100 % condensation point
Working altitude
2000 meters max.
(*)
Full power guaranteed up to Amb.T. = 50°C for PVI-10.0-I models, and 45°C
for PVI-12.0-I models (provided unit is not exposed to direct solar radiation)