Step 1: Remove the front cover of the inverter as shown in section 3.4.2.
Step 2: Pass the alarm or signal cables from the inverter terminal box outside, by
passing them through one of the holes on the bottom of the inverter.
Step 3: Connect the cables by following the serigraphy on the signal connector.
3.4.8
Selection of grid standard
WARNING: Before carrying out any operation, follow the
connection/disconnection procedure detailed in paragraph 3.4.1.
The inverter is provided with two selector switches (Fig. 13) which allow installers
to choose which grid standard they wish to apply. The unit is delivered with the
selector switches set in the ‘0’’0’ position (default setting). To allow AURORA to
operate regularly, installers must select the grid standard in accordance with the
national regulations.
To access the selector switches, remove the front cover as shown in paragraph
3.4.2.
NOTE: The ‘0’’0’ default position does not allow connection to the
power supply grid.