Gas/Air Valve Setup Procedure
Gas/Air Valve Setup Procedure
Procedure to correctly set new Air/Gas Valve
using a micro-manometer.
1. Loosen screw in outlet pressure test point
and connect to ‘+’ (positive) side of
differential micro-manometer.
Tee the ‘-’ (negative) side of the micro-
manometer into the air signal tube.
2. Remove special ⁄ BSP screw from flue
gas outlet (above heat exchanger) and
insert probe of combustion analyser
approximately 50 mm.
Temporarily seal probe into flue gas test
point.
3. Press ‘ADVANCE’ or central heating
‘SELECT’ button to obtain ON display in
programmer screen. Ensure any
connected room thermostat is calling for
heat. Observe burner lights and allow
boiler to operate in central heating mode
for several minutes.
4. Simultaneously press ‘+’ and ‘STEP’
buttons and hold down for 5 to 6 seconds.
After one minute, the boiler will be
operating at the correct reduced input rate
to enable the differential pressure to be set.
5. Ensure micro-manometer is in Pa or mbar
scale and has zeroed correctly. If in doubt,
re-zero the instrument.
6. Check differential pressure reading.
This should be zero or a negative (gas
relative to signal) value of 0 to - 5 Pa (0.00
to - 0.05 mbar).
Use zero adjustment screw (below central
dust cover) to reset differential if
necessary.
Note:
Turning adjustment screw clockwise
reduces negative differential; anti-
clockwise increases negative differential. A
4 mm hexagon key should be used to make
the adjustment.