ID-E342-001GB
109
11 STANDARD CONFIGURATION
The POLON 4500 control panel delivered to a customer has manufacturer's pre-programmed operation
modes defined as the standard configuration.
According to the standard configuration, a control panel is programmed as follows:
-
the MSL-1 module is declared;
-
the MSG-1 module is declared;
-
functions of the monitoring lines for the MSG-45 modules are programmed according to Table
9.3;
-
functions of the relay outputs for the MSG-45 modules are programmed according to Table 9.5;
-
all addressable elements (in the addressable space) have type 0 declared (are not reviewed by
the control panel);
-
addressable elements are potentially assigned to the zones with numbers compliant with
numbers of lines in which they are installed, with the group A programmed;
-
controlling, monitoring and signalling (EKS-4001, EWS-4001, SAL-4001) elements are not
configured; zones are not assigned (zone matrix empty); no variants;
-
all user messages assigned to the EKS-4001, EWK-4001 logical numbers – standard;
-
fire extinguishing zones (1 ÷ 4) are assigned with variant 15 (two-stage alarm with coincidence
including two fire warning devices), other zones are assigned with variant 2 (two-stage alarm);
-
all user messages assigned to zones – standard;
-
the PK1 relay (marked as PU) permanently programmed as an output signalling a general fault;
-
the PK2 output relay programmed as TYPE 3, variant 1 without delays (actuation in the event of
a 1
st
stage alarm occurrence in the control panel);
-
the PK3 output relay programmed as TYPE 2 (monitoring output);
-
other relays (PK4 ÷ PK8) and signal lines (LS1 ÷ LS4) programmed as TYPE 0 (inactive);
-
the PK relays and LS signal lines potentially without zone interdependence (zone matrix empty);
-
all LK monitoring lines programmed with variant 0 (inactive);
-
all user messages assigned to monitoring lines - standard;
-
the DR-48 printer not declared;
-
the T1 time (for ACKNOWLEDGEMENT ) set at 30 seconds;
-
the T2 time (for hazard recognition) set at 1 minute;
-
the T3 time (alarm output actuation delay) set at 0;
-
the time of automatic switching between the PERSONNEL PRESENT/PERSONNEL ABSENT
operation mode - not programmed;
-
factory access code at the 2
nd
level – 2222;
-
factory access code at the 3
rd
level – 3333;
-
factory access code at the 4
th
level – 3112;
-
event memory cleared.
11.1 USER CONFIGURATION PROGRAMMING
In order to adapt the control panel to operation compliant with the installation design, it is necessary to
program it individually. The panel must be programmed according to the programming manual (PM)
after obtaining the 3
rd
or 4
th
access level authorisation. The entered configuration data will also be
stored when the total power failure occurs.
Note:
After the control panel is programmed, the configuration data should be immediately sent to a
computer (using the configuration program) and saved.
Содержание 4000
Страница 25: ...ID E342 001GB 25 Fig 5 3 MSL 1M line module overview ...
Страница 96: ...96 ID E316 001GB Fig 9 16 Non potential output exemplary connection ...
Страница 101: ...ID E342 001GB 101 Fig 10 2 MSI 48 and MSI 48 Ed 3 network modules ...
Страница 103: ...ID E342 001GB 103 Fig 10 3 Four control panels network connection with two pairs of cables ...
Страница 104: ...104 ID E316 001GB Fig 10 4 Four control panels network connection with a pair of optical fibres ST type contact ...
Страница 105: ...ID E342 001GB 105 Fig 10 5 Four control panels network connection with two pairs of optical fibres SC PC type contact ...