118
ID-E316-001GB
14 OPERATION AND MAINTENANCE
14.1 PROPER USAGE REGULATIONS
The reliability of control panels depends on maintaining correct operating modes, supply voltage,
battery condition and carrying out periodical inspections.
The periodical inspections should be executed by the Authorised Service Station that was appointed by
the user to perform maintenance works. Any fault should be immediately reported to the Service
Station. While replacing fuses, attention should be paid to their nominal values. It is not allowed to
replace a burnt fuse with a spare fuse with a greater nominal value. This may damage the unit.
The following fuses are used in the POLON 4500 control panels:
a) in the power supply segment:
-
B1/10 A type T10L125 V – protection of the battery cluster circuit;
-
B2/3.15 A type T3, 15L250 V – protection of the + 24 V circuit supplying additional external
devices;
b) in the MSL-1M module:
-
B1/500 mA type F500L250 V – protection of MSL-1M;
c) in the PPW-45 module:
-
B1/1 A type F1L250 V – protection of PPW-45;
d) in the MSG-45 module:
B1/1 A type F1L250 V – protection of MSG-45.
14.2 PERIODICAL INSPECTIONS AND MAINTENANCE GUIDELINES
The POLON 4500 control panels periodical inspections, including the checks described in section 8.3,
must be carried out according to PN-E-08350-14:2002 standard at least once a year.
The condition of the screens, grounding or ground wiring (with the control panel housing) should be
inspected and the battery clamps should be cleaned every six months.
The battery charging level should be checked at least once a year. To this end, use the mains switch in
the AC power adaptor to disconnect the mains power supply for approx. 2 hours and, after the system is
reactivated, check if, during a period not longer than 5 hours, the power adaptor charges the battery
cluster and automatically switches to the buffering mode.
A correctly operating and regularly inspected control panel does not require any special maintenance
works. It is recommended to regularly remove dust from the control panel surfaces.
15 PACKAGING, TRANSPORTATION AND STORAGE
15.1 PACKAGING
A control panel is wrapped in a plastic bag and packed to a transport box made of 5-ply cardboard. The
following elements are also packed in the transport box:
-
control panel installation frame with fixing elements;
-
modules in individual packages;
-
spare parts;
-
descriptive documentation;
-
warranty certificate.
15.2 TRANSPORT GUIDELINES
Содержание 4000
Страница 25: ...ID E342 001GB 25 Fig 5 3 MSL 1M line module overview ...
Страница 96: ...96 ID E316 001GB Fig 9 16 Non potential output exemplary connection ...
Страница 101: ...ID E342 001GB 101 Fig 10 2 MSI 48 and MSI 48 Ed 3 network modules ...
Страница 103: ...ID E342 001GB 103 Fig 10 3 Four control panels network connection with two pairs of cables ...
Страница 104: ...104 ID E316 001GB Fig 10 4 Four control panels network connection with a pair of optical fibres ST type contact ...
Страница 105: ...ID E342 001GB 105 Fig 10 5 Four control panels network connection with two pairs of optical fibres SC PC type contact ...