5.7 DR-48 PRINTER
The DR-48 printer is used to register (in a printout form, on a paper band) the events which take place
when a facility is monitored by the POLON 4500 control panel.
The events include:
-
alarms;
-
faults and their removals;
-
fault or alarm acknowledgements;
-
switching the control panel operating mode from PERSONNEL PRESENT to PERSONNEL ABSENT
and vice versa;
-
delays switching on and off;
-
alarm resets;
-
testing;
-
disablements;
-
access to the configuration.
Each event message contains its date and time and a short description. Additionally, if a text message is
assigned to a zone (user's text), during an alarm of this fire protection element, apart from the line
number, element number and zone number, the assigned message is also printed out.
The POLON 4800 control panel stores 1,000 latest events that have been signalled. The stored events,
sorted by their date and time of occurrence may be printed after choosing a proper function on the
keypad according to the programming manual (PM).
On-going events recording on the paper tape and printing out the contents of the event memory is
possible only when the printer is assigned for operation in accordance with the programming manual
(PM). Regardless of assigning the printer to operation, the event memory is constantly updated.
See below for examples of incident printouts:
FAULT !
TERMISTOR IN TUN-4046 !
L-1 E-8 ZONE-31
2007-01-30 / 14:53:18
ACKNOWLEDGEMENT !
2007-01-30 14:54:00
FIRE ALARM WITH TUN-4046 !
L-1 E-98 ZONE-25
CONFERENCE HALL
2ND FLOOR
2007-01-30 17:20:00
** 1ST STAGE FIRE ALARM! **
2007-01-30 17:20:00
ACKNOWLEDGEMENT !
2007-01-30 17:22:30
----- ALARMU RESET -----
2007-01-30 17:25:17
The printer is equipped with a thermal paper roll (width 80 mm and max. diameter Ø 50 mm).
At the back of the printer on a panel, there are two monostable push buttons located (PAPER and
RESET) used for the following operations:
Содержание 4000
Страница 25: ...ID E342 001GB 25 Fig 5 3 MSL 1M line module overview ...
Страница 96: ...96 ID E316 001GB Fig 9 16 Non potential output exemplary connection ...
Страница 101: ...ID E342 001GB 101 Fig 10 2 MSI 48 and MSI 48 Ed 3 network modules ...
Страница 103: ...ID E342 001GB 103 Fig 10 3 Four control panels network connection with two pairs of cables ...
Страница 104: ...104 ID E316 001GB Fig 10 4 Four control panels network connection with a pair of optical fibres ST type contact ...
Страница 105: ...ID E342 001GB 105 Fig 10 5 Four control panels network connection with two pairs of optical fibres SC PC type contact ...