ID-E342-001GB
55
Variant 2 – file alarm input
The input activation by specific resistance clench or opening (depending on the input settled operation
mode) causes a fire alarm triggering in the control panel assigned zone (if the zone alarming variant
criteria requirements are met).
Variant 3 – functioning monitoring
The input activation by specific resistance clench or opening (depending on the input settled operation
mode) causes a non-maskable fault occurrence in the control panel.
Input monitoring variants are programmed only for an EWK that possesses a logical number.
Note:
After the standard configuration loading and automatic configuration performance, the EWK elements
are assigned to a special logical number 0, and after a number attribution, variant 0 is assigned, which
causes that such an element is inactive.
Detailed information concerning the EWK element is contained in the EWS-4001 ‘Installation and
Maintenance Manual’.
7.7 SAL-4001 ACOUSTIC SIGNALLING DEVICES DECLARATION
A SAL-4001 addressable acoustic signalling device is a line element equipped with a piezoelectric
transducer used to generate an acoustic signal.
The SAL proper programming consists in declaring a line element (similarly to fire warning devices),
assigning it to a logical number and assigning the type and actuation variant by means of this logical
number.
A logical number for the SAL element is selected from the 1 ÷ 250 range and assigned to an element in
order to make the SAL actuation variants dependent on different events in the control panel. Each SAL
type element may be assigned only to one logical number and vice versa. As far as the program is
concerned, a logical number for the SAL element is an approximate equivalent to a zone for fire
protection elements. The logical number connects the SAL with actuation variants.
The SAL-4001 operation results from the operation mode programmed for an element and the
piezoelectric transducer actuation variant.
The SAL-4001 entire programming procedure includes two stages:
Stage I:
SAL-4001 declaration consisting in assigning:
-
an element number (1 ÷ 127) using the automatic configuration or the configuration with
verification or the manual declaration procedures;
-
a logical number (1 ÷ 250);
-
an operation mode (it is factory set but may be changed - see below).
The operation mode is defined by the following element parameters (standard mode in bold print):
sound pattern –
type1
or type2 or type3;
battery power supply monitoring (YES or
NO
);
internal power supply monitoring (
YES
or NO).
The set of parameters defining an operation mode is directly connected with a line element and is
programmed while declaring the SAL element as a line element. An operation mode may always be
changed in the program.
Stage II:
The SAL-4001 logical configuration consisting in assigning:
Содержание 4000
Страница 25: ...ID E342 001GB 25 Fig 5 3 MSL 1M line module overview ...
Страница 96: ...96 ID E316 001GB Fig 9 16 Non potential output exemplary connection ...
Страница 101: ...ID E342 001GB 101 Fig 10 2 MSI 48 and MSI 48 Ed 3 network modules ...
Страница 103: ...ID E342 001GB 103 Fig 10 3 Four control panels network connection with two pairs of cables ...
Страница 104: ...104 ID E316 001GB Fig 10 4 Four control panels network connection with a pair of optical fibres ST type contact ...
Страница 105: ...ID E342 001GB 105 Fig 10 5 Four control panels network connection with two pairs of optical fibres SC PC type contact ...