36
ID-E316-001GB
Fig. 5.9 MIK-48 interfaces module
5.6.1 PORT 1, PORT 2, PORT 3 communication ports
Each of the serial ports may be used to operate with an external device, after a port type is declared. A
given port type may be declared only for one port. Type 5 (barcode reader) may only be declared for
PORT no. 3.
PORT TYPE: 0
- not declared port - inactive.
PORT TYPE: 1
- interoperation with a PC
Used to transmit or read the configuration by means of a PC - special software for the POLON 4000
control panels configuration must be used.
The transmission bitrate is 9600 bps.
PORT TYPE: 2
- interoperation with the PMC-4000 monitoring system
Used to operate with the monitoring station utilising the PMC-4000 digital monitoring protocol of the
POLON 4000 system.
Declared transmission bitrate: 2400 bps, 4800 bps, 9600 bps.
The PMC-4000 protocol makes it possible to supply a monitoring station with information regarding the
following events/occurrences:
-
fire alarms;
-
technical alarms and their resets;
-
2
nd
stage alarms;
-
reset;
-
acknowledgement;
Содержание 4000
Страница 25: ...ID E342 001GB 25 Fig 5 3 MSL 1M line module overview ...
Страница 96: ...96 ID E316 001GB Fig 9 16 Non potential output exemplary connection ...
Страница 101: ...ID E342 001GB 101 Fig 10 2 MSI 48 and MSI 48 Ed 3 network modules ...
Страница 103: ...ID E342 001GB 103 Fig 10 3 Four control panels network connection with two pairs of cables ...
Страница 104: ...104 ID E316 001GB Fig 10 4 Four control panels network connection with a pair of optical fibres ST type contact ...
Страница 105: ...ID E342 001GB 105 Fig 10 5 Four control panels network connection with two pairs of optical fibres SC PC type contact ...