ID-E342-001GB
9
Quiescent (detecting) mode
An operating condition in which the control panel is supplied from an electric energy source meeting
defined requirements and in which no other operation mode is signalled.
Alarm (fire) mode
An operating condition the control panel enters after receipt from warning devices information
regarding fire detection.
Preliminary alarm mode (first alarm mode)
An operating condition the control panel enters after warning devices transmits the first fire alarm
signal.
Disablement mode
An operating condition in which the control panel's reception of signals and generation of alarms from
any call points are intentionally disabled or the output from the control panel and/or the transmission
track to any fire alarm system elements which create the alarm installation are disabled.
Test mode
An operating condition in which the control panel signals that applicable functions are being checked.
Fault mode
A condition in which the control panel signals a fault in any element of the alarm installation or own
circuits.
Technical alarm mode
An operating condition in which the control panel signals actuation of any supervised external devices or
provides information regarding the service status of fire detectors.
POLON 4000 system digital monitoring (PMC-4000)
A digital monitoring protocol defined in the POLON 4000 control panels.
2 DEVICE COMPLETENESS
Table 2.1 lists the set of items which compose the POLON 4500 control panel furnishings.
See Table 2.2 for a list of fuses installed in the control panel.
Table 2.3 contains a list of additional equipment which may be installed in the POLON 4500 control
panels (ordered separately).
Table 2.1
Item
Description
Drawing (catalogue) No.
Quantity
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Complete casing
M1C-FES, 30V/10A mains power supply unit
MZ-48 power supply unit
PSC-46 central controller module
DR-48 printer
MSL-1M line module
PPW-45 programmable outputs module
MIK-48 interface module
PS-48 signalling devices board
PP-45 intermediate board
MSG-45 extinguishing control module
Frame - complete
Operation and Maintenance Documentation (OMD)
Servicing manual
Warranty certificate
Control panel package
A/E300-50.00.00-1
B/E270-50.00.00
B/E270-180.00.00-1
C/E270-40.00.00
B/E270-20.00.00
B/E316-20.10.00
B/E270-60.00.00
C/E270-80.00.00
C/E316-30.00.00
B/E316-10.00.00
D/E240-120.00.00.00-5
ID-E300-001
IO-E300-001
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Содержание 4000
Страница 25: ...ID E342 001GB 25 Fig 5 3 MSL 1M line module overview ...
Страница 96: ...96 ID E316 001GB Fig 9 16 Non potential output exemplary connection ...
Страница 101: ...ID E342 001GB 101 Fig 10 2 MSI 48 and MSI 48 Ed 3 network modules ...
Страница 103: ...ID E342 001GB 103 Fig 10 3 Four control panels network connection with two pairs of cables ...
Страница 104: ...104 ID E316 001GB Fig 10 4 Four control panels network connection with a pair of optical fibres ST type contact ...
Страница 105: ...ID E342 001GB 105 Fig 10 5 Four control panels network connection with two pairs of optical fibres SC PC type contact ...