ID-E342-001GB
93
fP Function
Time parameters
Actuation criterion
15 SEALING
SEALING ”Delay time”
Programmable time t4 = 0...120 s
counted from E.A. discharge
moment , PK actuation from t4 time
countdown until alarm reset
t4 time countdown
16 COMMON
ELECTROVALVE
”Pk COMMON ELECTROVALVE
activation time” Programmable
impulse t4 = 0...30 min.
EXTINGUISHING START
function actuation and
ELECTROVALVE1 or
ELECTROVALVE2 relay switch
on, in at least one (any)
extinguishing zone
Table 9.7 Default settings of relays, monitoring lines and time parameters after standard configuration
loading
Declared relays numbers
Relays assigned functions – fP
PK1
ELECTROVALVE 1
PK4
ACTUATION SIGNALLING CONTROL
PK5
EVACUATION SIGNALLING CONTROL
PK6
WARNING SIGNALLING CONTROL
Declared monitoring lines numbers
Monitoring lines functions names – fK
1
EXTINGUISHING START
3
EXTINGUISHING STOP
5
(ONLY) MANUAL CONTROL
Time parameters
PK „ELECTROVALVE 1” activation time
5 s
PK „ELECTROVALVE 2” activation time
5 s
PK „ELECTROVALVE 3” activation time
5 s
SEALING delay time
10 s
RESET disablement time
0 s
EXTINGUISHING delay time
60 s
PK „COMMON ELECTROVALVE” activation time
5 s
Содержание 4000
Страница 25: ...ID E342 001GB 25 Fig 5 3 MSL 1M line module overview ...
Страница 96: ...96 ID E316 001GB Fig 9 16 Non potential output exemplary connection ...
Страница 101: ...ID E342 001GB 101 Fig 10 2 MSI 48 and MSI 48 Ed 3 network modules ...
Страница 103: ...ID E342 001GB 103 Fig 10 3 Four control panels network connection with two pairs of cables ...
Страница 104: ...104 ID E316 001GB Fig 10 4 Four control panels network connection with a pair of optical fibres ST type contact ...
Страница 105: ...ID E342 001GB 105 Fig 10 5 Four control panels network connection with two pairs of optical fibres SC PC type contact ...