ID-E342-001GB
45
6.2.1 Automatic configuration
Elements located in the main loop are numbered consecutively starting from 1 from the side of the
terminals marked as Lx up to the closest branch. Next, the control panel numbers the elements located
in the branch to its end. After the numbering process is finished in the branch, the system returns to the
main loop and numbers the elements to the next branch and then continues numbering the elements
within the branch according to the above-mentioned procedure. This process includes all addressable
elements.
This numbering method always designates elements with numbers from 1 to n.
6.2.2 Configuration with verification
In this option, it is necessary (on the basis of the installation design and control panel numbering
algorithm) to pre-declare, i.e. define (by means of a keyboard or computer file) an element type for each
number within a given loop. Next, the verification option must be actuated in the control panel. If the
element types declared with given numbers are compliant with the element types numbered according
to the required algorithm, the control panel automatically numbers the addressable elements.
6.2.3 Manual number assigning
This method makes it possible to number addressable elements in any given way. In order to assign the
serial numbers to the element numbers, they may be entered in the serial numbers box manually or
using a barcode reader.
Manual declaration of numbers for the whole detection line ensures free configuration of the elements
located in this line (elements may be numbered in any order without maintaining continuity of the
numbering).
Note:
-
An ADC-4001 adapter with a wrongly defined operation mode may cause current overload of
the detection line. Should it happen, it is necessary to unplug the adapter from the socket and
wait at least 5 minutes. A re-installed adapter will only draw 150 μA from the line (the side line
is automatically disabled). Before the adapter side line is re-enabled, it must be entered in a
correct operation mode according to the programming manual (PM).
-
As the radio detectors constitute a line branch, the automatic configuration and configuration
with verification procedures are only possible if the adapter is located in the loop-shaped
detection line. If the adapter is connected to a radial line, the line must be set up manually.
Содержание 4000
Страница 25: ...ID E342 001GB 25 Fig 5 3 MSL 1M line module overview ...
Страница 96: ...96 ID E316 001GB Fig 9 16 Non potential output exemplary connection ...
Страница 101: ...ID E342 001GB 101 Fig 10 2 MSI 48 and MSI 48 Ed 3 network modules ...
Страница 103: ...ID E342 001GB 103 Fig 10 3 Four control panels network connection with two pairs of cables ...
Страница 104: ...104 ID E316 001GB Fig 10 4 Four control panels network connection with a pair of optical fibres ST type contact ...
Страница 105: ...ID E342 001GB 105 Fig 10 5 Four control panels network connection with two pairs of optical fibres SC PC type contact ...