TPC-101 

3-Phase Coupler 

 

1, 2, or 3 per system 

 

 

(one for each  

 

transformer) 

 

QUICK-START GUIDE 

INSTALLATION ESSENTIALS 

CHECK YOU HAVE EVERYTHING YOU NEED 

NMC-101 

Panel 

 

1 per system 
(Connects to 

existing Fire Alarm 

Control Panel

CHK-400 

Choke 

 

1 per system 

(provides filtered 

power to NMC

 

Laptop SSC 

software 

On the CD shipped 

with every system 

Laptop 

You will need to 

provide a laptop. It 

makes the job much 

faster 

USB-Serial 

Adapter Cable 

If your laptop has no 

DB9 serial port, you 

will need a USB-

serial adapter 

Instruction 

Manuals  

are provided in 

hard-copy and on 

the CD sent with 

every system 

Barcode 

scanner: 

Makes  

life much easier! 

Page 1 

 

 

 

 

 

ISD 2501UW or ISD-2501UWS 

Horn only or  

Horn & Strobe 

In-Suite Device (ISD) 

 

1 per suite or bedroom,  

or as per AHJ’s instructions 

Before making a sale, a Site Survey should be written up

 

after inspecting the building, and 

submitted  to  Signalink  Technical  Support.    An  approved  survey  ensures  that  your 
installation will be fast and easy.  Download from our websit

www.signalink.com

 

Fire-Link is relatively simple to install.  Nevertheless, it is a system and the installer needs to be 
trained.  Inadequate training leads to bad installations and unsatisfied customers:  

Signalink has an on-line training and certification process on its website, and is available 
by  email.   

Please  take  the  time  to  get  trained!

    It  only  takes  a  short  while, will  give  you 

satisfied customers, and will save your organization time and money 

Submit Site Surveys to: 

[email protected]

  

Fax 

(250) 491 3895 

Dealer Kit  includes these items 

Before going on-site: READ THIS SYSTEM GUIDE FIRST! 

Make sure you have the appropriate training, and a site survey 

Page 4 

Prepare the Job File 

Create a list of the ISD’s and their location—using a laptop 

 

· 

Laptop  and  barcode  scanner

:    Pre-load  the  Signalink  System  Configurator  (SSC) 

software  provided  on  CD  with  each  system.    Run  SSC  on  the  laptop.    Note:  the 
laptop with barcode scanner is not essential, but is highly recommended for speed 
of  installation,  accuracy  of  information,  and  to  have  a  computer  record  of  the  job 
details.  A Barcode Scanner and the Cable Adapter are available in the DEALER KIT 

· 

Scan the VID number of each ISD 

and write its intended location on the back label 

· 

Enter the job file, and set up the system

:  Consult 

077.0045 NMC Programming Manual.

  If using 

a laptop, also consult 

077.0046: Signalink System Configurator User’s Manual

 

Install the ISDs in each suite (See ISD Installation Q/S Guide) 

 

 

 

DO 

· 

Anchor each ISD using 4 
screws, if permitted 

· 

Check for a one flash per 
second blinking yellow 
STATUS light after plugging 
the ISD into a receptacle  

· 

Press the TEST button after 
plugging the ISD into a 
receptacle to test the  alarm 

· 

Instruct the tenant what the 
device is and what it does 

Do NOT: 

· 

Place the ISD over a 
source of heat such as a 
base board heater or hot air 
register 

· 

Place the ISD in direct sunlight 

· 

Install the ISD into a switched 
receptacle 

· 

Forget to leave behind the 
resident’s instruction “sleeve” to 
advise the resident what the 
device is and what it does 

· 

Introduce yourself:  and tell the resident what you are doing 

· 

Select a suitable AC outlet for best audibility, plug it in.  CAUTION!  
DO  NOT  PLUG  IT  INTO  AN  AC  OUTLET  THAT  CAN  BE  SWITCHED 
OFF!  FIX THE AC RECEPTACLE IF NEEDED FOR GOOD CONTACT 

· 

If no-one is sleeping, press TEST and let them hear the alarm 

· 

Explain the light will go green when the system is running 

Enroll the ISDs and Test & Verify System Operation 

 

 

· 

Ensure the system time and date is set correctly, and clear all the log files 

· 

Consult 

077.0045 NMC Programming Manual

 for Enrolment instructions.  The act of enrolling 

the  ISDs  is  fully  automatic,  and  allows  the  NMC  to  verify  that  all  ISDs  are  communicating 
properly, and that they have good AC power, a good battery, and that the buzzer is working 
properly (and strobe if fitted). 

· 

Test the complete system using the 

ISD TEST ALL

 function 

· 

If using the laptop, create and save a 

Commissioning Report

 

Explain the System to the Building Manager

 

 

· 

Give  him  or  her  document 

077.0025:  Building  Manager’s  Guide.

    Explain  how  to  silence 

troubles and how to resolve local troubles caused by residents’ behavior 

· 

Explain the trouble log “LOG” and “VIEW” features

:  to see which suite is in trouble  

TEST button 

STATUS light 

BUZZER 

 

NEED HELP?  CALL TECH SUPPORT (888) 765 7514 

[email protected]

 