ID-E342-001GB
49
-
a set of assigned EWK inputs if it is required by a given variant (range of assigned EWK elements:
1 ÷ 80, EWK inputs range: 1 ÷ 8 – only own control panel);
-
user messages for a technical alarm and non-maskable fault of monitoring inputs.
The EKS-4001 output relay activation variants
See Table 7.1 for the possibilities of programming the EKS output. The "control panel number"
parameter (only for control panels operating in a network) has the following meaning:
-
control panel number = 0 shows the dependence on an event in any control panel included in
the common detection area;
-
control panel number > 0 shows the dependence on an event from a given control panel
(provided it is included in the common detection area);
-
control panel number ”b” allows for making actuacon dependent only on local control panel
events.
For variants with additional zone dependencies: zone number = 0 shows the dependence on the total
number of events within all zones in a selected control panel included in the common detection area.
Table 7.1
Variant
Control
Panel
No.
Zones/EKS/EWK
Numbers
Actuation Criterion
0
b
b
Output inactive
1
0
b
1
st
stage general alarm
2
0 ÷ 31
0 ÷ 1024
‘union’ of 1
st
stage alarms in assigned zones
3
0 ÷ 31
0 ÷ 1024
‘conjunction’ of 1
st
stage alarms in assigned zones
4
0
b
2
nd
stage general alarm
5
0 ÷ 31
0 ÷ 1024
‘union’ of 2
nd
stage alarms in assigned zones
6
0 ÷ 31
0 ÷ 1024
‘conjunction’ of 2
nd
stage alarms in assigned zones
7
0
b
general fault in control panel
8
0
b
Non-maskable general fault in control panel
9
0
b
general technical alarm in control panel
10
b
1 ÷ 250
‘union’ of faults of assigned EKS inputs
11
b
1 ÷ 250
‘union’ of non-maskable faults of assigned EKS inputs
12
b
1 ÷ 250
‘union’ of technical alarms of assigned EKS inputs
13
b
1 ÷ 80
‘union’ of faults of assigned EWK inputs
14
b
1 ÷ 80
‘union’ of technical alarms of assigned EWK inputs
15
b
b
reset output
16
b
b
alarming device – 1
st
stage general alarm
17
b
0 ÷ 1024
alarming device – ‘union’ of 1
st
stage alarms in assigned zones
Variant 0
-
No EKS actuation criterion (output permanently deactivated).
Variant 1 – general 1
st
stage alarm
Содержание 4000
Страница 25: ...ID E342 001GB 25 Fig 5 3 MSL 1M line module overview ...
Страница 96: ...96 ID E316 001GB Fig 9 16 Non potential output exemplary connection ...
Страница 101: ...ID E342 001GB 101 Fig 10 2 MSI 48 and MSI 48 Ed 3 network modules ...
Страница 103: ...ID E342 001GB 103 Fig 10 3 Four control panels network connection with two pairs of cables ...
Страница 104: ...104 ID E316 001GB Fig 10 4 Four control panels network connection with a pair of optical fibres ST type contact ...
Страница 105: ...ID E342 001GB 105 Fig 10 5 Four control panels network connection with two pairs of optical fibres SC PC type contact ...