ID-E342-001GB
69
Clearing the optical and acoustic signals (FAULT) takes place automatically after the fault is removed.
The FAULT acoustic signalling is dis-actuated after pressing the backlit ACKNOWLEDGEMENT button.
Information regarding the detected faults is provided on the display. If, during 10 minutes from the
latest registered fault occurrence, there is no new fault, the LCD display is dis-actuated. If the display is
dis-actuated, the currently detected faults may be viewed after pressing the FAULT push button. Then
the display will present fault messages. If the number of messages exceeds the display capability, they
may be scrolled using the same push button or ↓↑ push bunons.
The exception from this rule are non-maskable faults in (properly programmed) monitoring circuits of LK
monitoring lines or the EKS-4001 monitoring and controlling elements whose messages are
automatically presented on the display until they are cleared.
If a printer is provided for operation, a message regarding a given fault will be printed on a paper tape
after it is detected.
8.2.1 Fault types
1. System faults:
-
program memory, RAM memory or CONFIGURATION fault;
-
microprocessor operation interference.
2. Microprocessor module faults:
-
microprocessor controller for the LCD display and operator's console fault;
-
the MSL-1 module microprocessor controller fault;
-
loss of communication with the controller for the LCD display and operator's console;
-
loss of communication with the MSL-1 module controller;
-
loss of communication with the controller for the following modules: MSG-1, MSG-2, MSG-3 and
MSG-4;
-
non-declared MSL-1 module if connected;
-
non-declared MSG-1, MSG-2, MSG-3 or MSG-4 module if connected.
3. Detection line faults:
-
line processor fault;
-
line output short circuit;
-
loop output short circuit;
-
break in a detection line;
-
detection line earth fault;
-
number of line elements in a detection loop exceeding 127;
-
presence of not declared elements in a detection line;
-
incorrect parameters for the detection loop (resistance, capacity);
-
no response from a line element to a query from the control panel;
-
multiple declaration of the same line element.
4. Line element faults:
-
measuring element fault;
-
short circuit isolator actuated;
-
EEPROM memory fault;
-
EKS output line fault;
-
IN1 EKS input line fault;
-
IN2 EKS input line fault;
-
IN1 EKS non-maskable fault;
-
IN2 EKS non-maskable fault;
-
EWS relay fault;
-
battery of SAL external power adaptor fault.
Содержание 4000
Страница 25: ...ID E342 001GB 25 Fig 5 3 MSL 1M line module overview ...
Страница 96: ...96 ID E316 001GB Fig 9 16 Non potential output exemplary connection ...
Страница 101: ...ID E342 001GB 101 Fig 10 2 MSI 48 and MSI 48 Ed 3 network modules ...
Страница 103: ...ID E342 001GB 103 Fig 10 3 Four control panels network connection with two pairs of cables ...
Страница 104: ...104 ID E316 001GB Fig 10 4 Four control panels network connection with a pair of optical fibres ST type contact ...
Страница 105: ...ID E342 001GB 105 Fig 10 5 Four control panels network connection with two pairs of optical fibres SC PC type contact ...