ID-E342-001GB
61
The "control panel number" parameter (only for control panels operating in a network) has the
following meaning:
control panel number = 0 shows the dependence on an event in any control panel included in the
common detection area;
control panel number > 0 shows the dependence on an event from a given control panel (provided it is
included in the common detection area);
control panel number ”b” allows for making actuacon dependent only on local control panel events.
For variants with additional zone dependencies: zone number = 0 shows the dependence on the total
number of events within all zones in a selected control panel included in the common detection area.
Table 7.6
Variant
Control
Panel
No.
Zone
number
Actuation Criterion
0
b
b
inactive output
1
0
b
general 1
st
stage alarm
2
0 ÷ 31
0 ÷ 1024
‘union’ of 1
st
stage alarms in assigned zones
3
0 ÷ 31
0 ÷ 1024
‘conjunction’ of 1
st
stage alarms in assigned zones
4
0
b
general 2
nd
stage alarm
5
0 ÷ 31
0 ÷ 1024
‘union’ of 2
nd
stage alarms in assigned zones
6
0 ÷ 31
0 ÷ 1024
‘conjunction’ of 2
nd
stage alarms in assigned zones
Variant 0
Means lack of an actuation criterion (permanently non-activated output).
Variant 1 – general 1st stage alarm
The output activation is performed in the case of a
1
st
stage alarm occurrence in the control panel or any
control panels of the common supervision area.
Variant 2 – ‘union’ of 1
st
stage alarms in assigned zones of the common supervision area control
panels
The output activation is performed in the case of a
1
st
stage alarm occurrence in at least one zone that is
assigned to this relay.
Variant 3 – ‘conjunction’ of 1
st
stage alarms in assigned zones of common supervision area control
panels
The output activation is performed in the case of a
1
st
stage alarm occurrence in at least two zones that are
assigned to this relay.
Variant 4 – general 2
nd
stage alarm
The output activation is performed in the case of a 2
nd
stage alarm occurrence in the control panel or any
control panels of the common supervision area.
Variant 5 – ‘union’ of 2
nd
stage alarms in assigned zones of the common supervision area control
panels
The output activation is performed in the case of a 2
nd
stage alarm occurrence in at least one zone that is
assigned to this relay.
Variant 6 – ‘conjunction’ of 2
nd
stage alarms in assigned zones of common supervision area control
panels
Содержание 4000
Страница 25: ...ID E342 001GB 25 Fig 5 3 MSL 1M line module overview ...
Страница 96: ...96 ID E316 001GB Fig 9 16 Non potential output exemplary connection ...
Страница 101: ...ID E342 001GB 101 Fig 10 2 MSI 48 and MSI 48 Ed 3 network modules ...
Страница 103: ...ID E342 001GB 103 Fig 10 3 Four control panels network connection with two pairs of cables ...
Страница 104: ...104 ID E316 001GB Fig 10 4 Four control panels network connection with a pair of optical fibres ST type contact ...
Страница 105: ...ID E342 001GB 105 Fig 10 5 Four control panels network connection with two pairs of optical fibres SC PC type contact ...