5.5.8 Reset output (TYPE 6)
The reset output supports only relays and its objective is to generate a reset impulse (duration approx. 4
seconds), after a fire alarm reset. This type may be used, e.g. to power supply or reset of detectors
requiring
a
separate
power
supply
source,
e.g.
flame
detectors
manufactured
by
Det-Tronics.
5.5.9 LK monitoring input
Each of the POLON 4500 control panel four monitoring inputs for may be programmed in the following
variants:
-
to monitor the actuation of external devices after receiving an actuation criterion from a
declared relay output or potential output (for TYPE-1, TYPE-2, TYPE-3 outputs);
-
to monitor the proper operation of external devices;
-
as a technical alarm input.
The input condition is analysed on the basis of the monitoring line characteristic resistance
measurement (Table 5.9). The range of the characteristic resistance (including the connecting cables
resistance) is 2.7 kΩ - 16 kΩ. If the monitoring line resistance is outside the defined range, this condition
is interpreted as an acknowledgement of external devices actuation (variant 1) or external devices fault
(variant 2).
In the control panel, improper conditions are signalled as faults in the following cases:
-
no acknowledgement of external device actuation with an active actuation signal of a declared
relay or potential output;
-
detection of an external device fault.
Table 5.9
Variant
Function
PK or LS assigned
output
Mode dependent on detection line characteristic
resistance
1
Actuation
monitoring
Activated
Non-maskable fault
2k7< R < 16 k
Technical alarm
R <0,9 k R > 30 k
Non-activated
Quiescent mode
2k7< R < 16 k
Technical alarm
R <0,9 k R > 30 k
2
Functioning
inspection
-
Quiescent mode
2k7< R < 16 k
Non-maskable fault
R <0,9 k R > 30 k
3
Technical
alarm
-
Quiescent mode
2k7< R < 16 k
Technical alarm
R <0,9 k R > 30 k
R – characteristic resistance of detection lines together with connecting cables
Monitoring inputs programming variants
Variant 1:
A monitoring line input may be assigned to one of the previously declared outputs (relay or potential)
defined as TYPE-1, TYPE-2, TYPE-3. Then, this input may be used to monitor external devices actuation
after receiving an actuation criterion from the declared output. Monitoring is enabled approx. 60
seconds after the monitored output is actuated (permissible time of the controlled device actuation
delay). Examples of using a monitoring input assigned to a relay or potential output are shown in Fig. 5.6
and 5.7.
Variant 2:
Содержание 4000
Страница 25: ...ID E342 001GB 25 Fig 5 3 MSL 1M line module overview ...
Страница 96: ...96 ID E316 001GB Fig 9 16 Non potential output exemplary connection ...
Страница 101: ...ID E342 001GB 101 Fig 10 2 MSI 48 and MSI 48 Ed 3 network modules ...
Страница 103: ...ID E342 001GB 103 Fig 10 3 Four control panels network connection with two pairs of cables ...
Страница 104: ...104 ID E316 001GB Fig 10 4 Four control panels network connection with a pair of optical fibres ST type contact ...
Страница 105: ...ID E342 001GB 105 Fig 10 5 Four control panels network connection with two pairs of optical fibres SC PC type contact ...