PSEN op2H-SL Series
Operating Manual PSEN op2H-SL Series
1004304-EN-01
40
1
2
EDM/3
RES
OSSD
PWR
Meaning
yel-
low
yel-
low
red
green
Error in OSSDs.
Check the ambient conditions and the wir-
ing.
Switch the safety light grid off and then on
again.
Supply voltage error.
Ensure that the supply voltage corresponds
to the information in the
Technical
details [
43]
.
Transmitter
1
2
3
TX
PWR
Meaning
yel-
low
green
Ready for operation
yel-
low
green
Internal error.
Check the ambient conditions and the wir-
ing.
Switch the safety light grid off and then on
again.
yel-
low
green
Error in the synchronisation of the light
beams.
Check the ambient conditions and the wir-
ing.
Switch the safety light grid off and then on
again.
yel-
low
yel-
low
green
Error in cascading.
Check the cascading and the wiring for the
cascading.
yel-
low
yel-
low
green
Error in restart function.
Check the ambient conditions and the wiring
for the start button.
Switch the safety light grid off and then on
again.
Safety light grid restart
a
Disconnect the supply voltage from the safety light grid and reconnect it. The
automatic
restart [
11]
begins.