PSEN op2H-SL Series
Operating Manual PSEN op2H-SL Series
1004304-EN-01
35
7. Tighten the screws on the brackets with the max.
torque [
43]
.
}
Check that the green LED on the receiver is lit.
}
Check that the safety light grid operates correctly.
If a single light beam is interrupted by an opaque object
– the green LED must go out,
– the red LED must light and
– the safety light grid must switch to a safe state.
}
For this test you should use a test rod for a safety light grid with a resolution of 24 mm.
LED indicators in alignment mode
1
2
EDM/3
RES
OSSD
PWR
Meaning
red
green
Safety light grid not aligned, no synchron-
isation of first and last light beams.
yel-
low
red
green
Synchronisation of first and last light beams.
One or more light beams are interrupted.
yel-
low
yel-
low
green green
Synchronisation of first and last light beams.
Weak signal strength.
Protected field is clear.
yel-
low
yel-
low
yel-
low
green green
Synchronisation of first and last light beams.
Medium signal strength.
Protected field is clear.
yel-
low
yel-
low
yel-
low
yel-
low
green green
Synchronisation of first and last light beams.
Medium signal strength.
Protected field is clear.
Commissioning
System connection
Make sure that the selected evaluation device has the following properties:
}
2-channel with feasibility monitoring
}
OSSD signals are evaluated
Suitable Pilz evaluation devices are, for example:
}
PNOZelog for monitoring safety light grids
}
PNOZsigma for monitoring safety light grids
}
PNOZ X for monitoring safety light grids