PSEN op2H-SL Series
Operating Manual PSEN op2H-SL Series
1004304-EN-01
30
}
Use separate cables to connect the wires to the OSSDs on different safety light grids or
safety switches.
}
For supply voltage, use only PELV/SELV power supplies that have a voltage buffer in
accordance with EN 60204-1.
}
The power supply must be able to bridge a short (20 ms) supply voltage failure in ac-
cordance with EN 61496-1.
}
The protection type (see
Technical details [
43]
) can only be achieved by using the
Pilz connection leads available as an accessory.
}
Connection to evaluation devices
– Use the cables listed in the order reference (see
Order references for
accessories [
51]
)
– The clamps for connection to the evaluation device must be kept in a locked control
cabinet. This prevents unauthorised modifications.
}
Ensure compliance with permissible cable bending radii (see
Technical
details [
43]
).
Connector pin assignment
Transmitter and receiver electrical connections are made with M12 connectors. These con-
nectors are located on the bottom of the transmitters and receivers.
}
Ensure that the wiring has been performed as indicated.
5-pin connector on the transmit-
ter
PIN
Assignment
Cable colour
1
2
5
3
4
1
+24 VDC
brown
2
Restart
Configuration of the type of
restart or activation of align-
ment mode
white
3
0 VDC
blue
4
Reserved
black
5
Start button
grey
5-pin connector on the receiver
PIN
Assignment
Cable colour
1
2
5
3
4
1
+24 VDC
brown
2
OSSD 1
white
3
0 VDC
blue
4
OSSD 2
black
5
EDM
Activation/deactivation of
EDM function
grey