PSEN op2H-SL Series
Operating Manual PSEN op2H-SL Series
1004304-EN-01
19
}
The height of the deviating mirror must be at least 100 mm greater than the protected
field height of the safety light grid.
}
You should not use more than one mirror per device.
}
Any dust or dirt on the mirror’s reflective surface will drastically reduce the operating
range.
Number of mirrors per device
Maximum operating range [
43]
in
m
1
4.8 m
Cascaded safety light grid
Minimum distance for cascaded safety light grids
When safety light grids are cascaded with two slave units, be sure to maintain the minimum
distance between the master unit and slave unit 2.
Width of the protected field
Minimum distance
< 3 m
263 mm
> 3 m
see
Minimum distance between parallel,
aligned safety light grids [
17]
Resolution for cascaded safety light grids
When safety light grids are cascaded, the resolution may vary from that stated in the tech-
nical details, depending on the brackets used for installation.
Installation using C-brackets
[2]
[1]
Legend
[1] Unchanged resolution of 24 mm at the ends of the safety light grid
[2] C-brackets